Daikin Air Conditioner Error Codes

Find your code in the list below. Each page explains what the code means, the most likely causes, step-by-step fixes you can do yourself, and the parts that commonly resolve it. 84 codes covered.

Finding your model number: it is on the unit's rating plate.

Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.

Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS)

CodeWhat it meansCheck first
A0A0 means an external protection device has activated (SM-TS3). Some indoor units carry an input for an…External protection device (e.g. condensate safety switch) activated›
A1A1 is an indoor unit PCB abnormality — the indoor control board itself has failed its self-checks (operation…Defective indoor unit PCB›
A3A3 is a drain level control system abnormality (SM-TS3; the owner manuals phrase it 'drain pump abnormal').…Clogged drain line (the first listed cause)›
A5A5 is the indoor coil protection control: in cooling it is freeze-up protection (the indoor heat exchanger…Clogged indoor air filter (Daikin's documented check order puts airflow first)›
A6A6 is an indoor fan motor abnormality. The control watches the fan's rotation speed through its Hall sensor…Layer short inside the fan motor winding›
A7A7 is a malfunction of the swing flap motor (SM-TS3) — the motor that drives the horizontal louver sweeping…Swing flap obstructed or jammed›
A8A8 is a malfunction of the power supply or AC input overcurrent on the indoor side (SM-TS3). The indoor…Supply voltage problem reaching the indoor unit›
A9A9 is a malfunction of the electronic expansion valve (SM-TS3) on models whose expansion valve is on the…Defective electronic expansion valve coil›
AAAA is a heater overheat (SM-TS3), and it applies only to ductless models fitted with an auxiliary electric…Blocked airflow over the heater (clogged filter, closed/blocked outlet)›
AFAF is a malfunction of a humidifier system (SM-TS3), on the ductless models that carry a built-in humidifying…Humidifier unit fault (water supply, tank or internal component)›
AHAH is a malfunction of the dust collector of the air cleaner (SM-TS3); the owner manuals phrase it…Dust collector saturated/dirty beyond its cleaning interval›
AJAJ is a malfunction of the capacity setting on the indoor unit PCB (SM-TS3). Replacement indoor boards ship…Capacity setting never made after an indoor PCB replacement›
C1C1 is a failure of transmission between the indoor unit PCB and its sub PCB (SM-TS3) — an internal link…Loose or damaged interconnect between the indoor PCB and sub PCB›
C3C3 is a malfunction of the drain level sensor (listed in the SM-TS3 summary grid). It is the sensor-side…Defective drain level sensor (float sensor)›
C4C4 is an indoor heat exchanger thermistor abnormality. The service manual decides it electrically: during…Thermistor connector disconnected›
C5C5 is a malfunction of the gas pipe thermistor for the heat exchanger (SM-TS3); Daikin's owner-manual list…Thermistor connector disconnected›
C6C6 is a malfunction of the fan motor sensor or the fan control driver (SM-TS3) — the sensing/driving…Defective fan motor speed (Hall) sensor›
C7C7 is a front panel driving motor fault (SM-TS3); the owner-manual list for the same code says 'louver limit…Panel/louver obstructed or knocked out of alignment›
C9C9 is the room temperature thermistor abnormality — the sensor that samples the air entering the indoor unit…Thermistor connector disconnected›
CACA is a malfunction of the discharge air thermistor (SM-TS3) — the sensor that measures the air temperature…Thermistor connector disconnected›
CCCC is a malfunction of the humidity sensor system (SM-TS3), on models that sense room humidity for…Defective humidity sensor›
CJCJ is an abnormality of the room temperature thermistor inside the remote controller (SM-TS3). On systems…Defective thermistor in the remote controller›
E0E0 means protection devices have activated — the unified summary (SM-TS3 grid) for the outdoor unit's…A protection device actuated (high/low pressure, overload, or temperature control)›
E1E1 is an outdoor unit PCB abnormality — the outdoor control board itself is defective (operation manual…Defective outdoor unit PCB›
E3E3 is actuation of the high pressure switch (HPS) — the safety switch has opened because refrigerant pressure…Dirty outdoor unit heat exchanger (SM-TS3's first cause)›
E4E4 is actuation of the low pressure switch (LPS) — suction pressure has fallen below the safe limit (SM-TS3…Abnormally low pressure drop (refrigerant loss or restriction)›
E5E5 is activation of the compressor overload (OL) protection — the wording is 'OL started,' and SM-TS3's…Defective discharge pipe thermistor›
E6E6 is compressor lock: at start-up, the position detection circuit and current waveform show the compressor…Compressor locked (mechanically seized)›
E7E7 is a DC fan lock on the outdoor unit: the fan motor was commanded to run but did not start within about…Foreign matter stuck in the outdoor fan›
E8E8 is input overcurrent detection (service manual SiUS091133; SM-TS3: 'overcurrent of inverter compressor').…Inverter compressor drawing excess current (mechanical load, failing compressor)›
E9E9 is a malfunction of the electronic expansion valve coil (SM-TS3; owner manuals: 'EXV error'). The…Defective expansion valve coil (open/shorted)›
EAEA is a four-way valve abnormality, 'cooling-heating switching error.' The four-way valve is the sliding…Defective four-way valve (stuck or not shifting)›
F3F3 is discharge pipe temperature control: the compressor's discharge pipe thermistor has exceeded its…Defective discharge pipe thermistor (or outdoor heat exchanger / outdoor air›
F6F6 is high pressure control in cooling. On the FTXS/FDXS LV pair — which carries no physical high-pressure…Abnormally high pressure in cooling (dirty outdoor coil, blocked airflow, overcharge)›
H0H0 is a compressor system sensor abnormality — a summary code the outdoor control sets when one of the…Defective sensor in the compressor system (thermistor group)›
H1H1 carries a dual definition in SM-TS3: a malfunction of the room temperature sensor, or of a humidifier unit…Defective room temperature sensor (applicable systems)›
H3H3 is a malfunction of the high pressure switch itself (SM-TS3) — the switch as a component has failed (its…Defective high pressure switch›
H4H4 is a malfunction of the low pressure switch itself (SM-TS3) — the component has failed, as distinct from…Defective low pressure switch›
H5H5 is a malfunction of the compressor motor overload thermistor (SM-TS3 detail pages) — the temperature…Defective compressor overload thermistor›
H6H6 is a position sensor abnormality — in fuller wording, 'operation halt due to faulty position detection…Defective position detection sensor circuit›
H7H7 is a malfunction of the outdoor unit fan motor signal (SM-TS3); Daikin's owner-manual list adds 'fan motor…Defective outdoor fan motor (signal/feedback section)›
H8H8 is a DC voltage/current sensor abnormality. The service manual assigns it by size class: on the 09/12…Defective DC voltage/current sensor circuit (09/12 class)›
H9H9 is the outdoor temperature thermistor abnormality (service manual SiUS091133; SM-TS3: 'malfunction of…Thermistor connector disconnected›
How to Read the Error CodeDaikin ductless units do not show their fault code on a display — the indoor unit just stops with its…The unit has stopped on a malfunction and is holding a code (the blinking OPERATION›
J1J1 is a malfunction of the pressure sensor (SM-TS3) — the electronic pressure transducer the outdoor control…Defective pressure sensor›
J2J2 is a malfunction of the current sensor of the compressor (SM-TS3) — the sensor that reports compressor…Defective compressor current sensor›
J3J3 is a discharge pipe thermistor abnormality — the sensor on the compressor's discharge line is reading out…Thermistor connector disconnected›
J4J4 is a malfunction of the low-pressure equivalent saturated temperature sensor system (SM-TS3). Rather than…Defective sensor in the low-pressure saturation sensing chain›
J5J5 is a malfunction of the suction pipe thermistor (SM-TS3) — the sensor on the suction line reads out of…Thermistor connector disconnected›
J6J6 is the outdoor heat exchanger thermistor abnormality — the sensor clipped to the outdoor coil reads out of…Thermistor connector disconnected›
J7J7 is a malfunction of a refrigerant-circuit thermistor — SM-TS3 groups J7/J8 as the liquid pipe (1)…Thermistor connector disconnected›
J8J8 is a malfunction of a refrigerant-circuit thermistor — SM-TS3 groups J7/J8 as the liquid pipe (2)…Thermistor connector disconnected›
J9J9 is a malfunction of the gas pipe thermistor in the refrigerant circuit (SM-TS3 groups J7/J8 as liquid pipe…Thermistor connector disconnected›
JAJA is a malfunction of the high pressure sensor (SM-TS3) — the electronic transducer on the high side reads…Defective high pressure sensor›
JCJC is a malfunction of the low pressure sensor (SM-TS3) — the low-side transducer reads faulty on…Defective low pressure sensor›
L0L0 is a malfunction of the inverter system (SM-TS3 summary grid) — the umbrella code for the outdoor inverter…Inverter system fault not specific to one sub-code›
L1L1 is a malfunction of the inverter PCB (SM-TS3 summary grid) — the inverter board itself, as distinct from…Defective inverter PCB›
L3L3 is an electrical box temperature rise (operation manual: 'electrical parts heat fault'). The outdoor…Blocked airflow through the outdoor unit's electrical box area›
L4L4 is a radiation fin temperature rise — the inverter's heatsink (the 'radiation fin' the power devices are…Radiation fin (heatsink) not cooling the inverter — blocked airflow or fouled heatsink›
L5L5 is output overcurrent detection — SM-TS3 specifies it as inverter instantaneous overcurrent on the DC…Instantaneous overcurrent on the inverter output (compressor drawing a current spike)›
L6L6 is inverter instantaneous overcurrent on the AC output (SM-TS3). It is L5's sibling: L5 watches the…Instantaneous overcurrent in the inverter's AC output›
L8L8 is a malfunction of overcurrent of the inverter compressor (SM-TS3) — the inverter is reporting that the…Compressor drawing excess current (mechanical load or failing compressor)›
L9L9 is a malfunction of inverter compressor startup — SM-TS3 calls it a startup error (stall prevention). The…Compressor stalling at start (mechanical)›
LALA is a malfunction of the power transistor (SM-TS3) — the inverter's output power devices themselves. This…Failed power transistor in the inverter output stage›
LCLC is a malfunction of transmission between the control PCB and the inverter PCB (SM-TS3) — the outdoor…Loose or damaged interconnect between control and inverter PCBs›
P1P1 is a power voltage imbalance, or an inverter PCB malfunction (SM-TS3 gives the code both readings). The…Power voltage imbalance in the supply›
P3P3 is a malfunction of the thermistor in the switch box (SM-TS3) — the temperature sensor inside the outdoor…Thermistor connector disconnected›
P4P4 is a radiation fin thermistor abnormality — the sensor that watches the inverter heatsink's temperature is…Defective radiation fin thermistor›
P9P9 is listed in SM-TS3's detail pages as a malfunction of the fan motor, in the context of the auto-charge…Defective fan motor (auto-charge system context)›
PJPJ is a malfunction of the capacity setting on the outdoor unit PCB, or an improper combination between the…Capacity setting wrong or unset after an outdoor PCB replacement›
U0U0 means refrigerant shortage. It is detected indirectly — from compressor current, discharge pipe…Refrigerant shortage from leakage (the headline cause)›
U1U1 is a reverse phase / open phase fault in the power supply (SM-TS3). The system has detected that its…Reversed phase in the supply wiring›
U2U2 is a voltage detection fault: the service manual defines it as low-voltage detection or over-voltage…Supply voltage not as specified (genuinely low or high mains)›
U3U3 means the check operation has not been executed, or a transmission error occurred in that context…Check operation never run after installation›
U4U4 is a signal transmission error between the indoor unit and the outdoor unit — it is detected when the data…Wiring error or broken indoor-to-outdoor connection wires (the No. 3 signal wire is the›
U5U5 is a malfunction of transmission between the indoor unit and the remote controller (SM-TS3). It belongs to…Broken or loose wiring between the wired remote and the indoor unit›
U6U6 is a malfunction of transmission between indoor units (SM-TS3). It belongs to multi systems, where indoor…Broken or miswired interconnect between indoor units›
U7U7 is a signal transmission error on the outdoor unit PCB itself (service manual SiUS091133, on the 24/30/36…Defective outdoor unit PCB (transmission section)›
U8U8 is a malfunction of transmission between remote controllers — the main/sub link on systems fitted with two…Broken or loose main/sub remote wiring›
U9U9 is a malfunction of transmission involving another system (SM-TS3): the indoor-outdoor transmission of a…Cross-connected transmission wiring between two systems›
UAUA is the indoor-outdoor combination fault. Daikin's documents phrase it three ways that all describe the…Wrong models interconnected (indoor and outdoor units not a compatible combination)›
UFUF means the check operation has failed to execute / the system is not set yet (SM-TS3). Like U3, it is a…Check operation not completed after installation›
UHUH is a malfunction of the system itself (SM-TS3): improper transmission wiring between the indoor and…Improper indoor-outdoor transmission wiring›
Won't Turn OnA Daikin ductless unit that will not turn on is usually not being given power, not being given a command, or…Breaker off or fuse blown (the first check)›