Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) C5 Error Code

What the C5 code means

C5 is a malfunction of the gas pipe thermistor for the heat exchanger (SM-TS3); Daikin's owner-manual list for the same code says 'indoor heat exchanger (2) thermistor short/open.' It is the second indoor coil thermistor — C4 watches the liquid pipe side, C5 the gas pipe side — and it is decided the same electrical way: the sensor circuit is open, shorted or disconnected. This code belongs to Daikin's unified residential ductless malfunction table (SM-TS3), shared across the FTXS/FDXS/FTXM/RMXS families; pull it with the remote self-diagnosis before acting on it.

Likely causes

  1. Thermistor connector disconnected
  2. Defective gas pipe thermistor
  3. Defective indoor unit PCB

How to fix it — step by step

  1. Confirm the code with the remote self-diagnosis first (hold TIMER CANCEL for 5 seconds until 00 shows, then press it repeatedly until the long beep marks the stored code), then breaker OFF before opening the indoor unit
  2. Locate the gas pipe thermistor on the indoor coil and check its connector is fully seated — disconnection is the standard first cause for Daikin's thermistor codes
  3. Test it against Daikin's thermistor chart: about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C, judged at the sensor's actual temperature. Open, shorted or far off-chart condemns the thermistor — replace it
  4. If the thermistor conforms and is connected, the indoor PCB is misreading it — hand a shop the pinpoint with the resistance you measured

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the C5 code

Parts run $25–$400Typical pro repair $450–$2,000Fixing it yourself typically saves $50–$1,975

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

Before you buy: check the gas pipe thermistor first

Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).

A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.

Test values from manualshelf.com documentation - confirm against your model's own tech sheet.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.

Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes

See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →