Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) E5 Error Code

What the E5 code means

E5 is activation of the compressor overload (OL) protection — the wording is 'OL started,' and SM-TS3's wording is 'inverter compressor motor or overheat.' The compressor is working beyond its safe load and the protection keeps tripping until the system shuts down; it resets only after roughly an hour of clean running. Note the boundary with E6: a compressor that locks at start-up is E6, while E5 is the overload protection tripping on a compressor that runs — lock is folded into E5 in some other documents, which is why both pages cross-refer. Everything past the thermistor check is sealed-system and inverter work.

Likely causes

  1. Defective discharge pipe thermistor
  2. Defective electronic expansion valve or its coil
  3. Defective four-way valve or its coil
  4. Refrigerant shortage
  5. Water mixed into the refrigerant
  6. Defective stop valve
  7. Defective outdoor unit PCB

How to fix it — step by step

  1. Confirm E5 with the remote self-diagnosis. Do not keep resetting and running it: repeated E5 events are what lock the system out, and an overloaded compressor is being damaged while it struggles
  2. Breaker off. First check: the discharge pipe thermistor — confirm it is connected (a disconnected thermistor is the first flowchart item) and test it against the thermistor chart (Check No. 01); a failed discharge thermistor is replaced
  3. The remaining checks are the technician's circuit walk, in this order: Check No. 12 electronic expansion valve, Check No. 13 four-way valve, then Check No. 14 the refrigerant line — shortage, water mixed in the refrigerant, and the stop valves
  4. If the thermistor, expansion valve, four-way valve and refrigerant line all pass, the documented remainder is the outdoor unit PCB
  5. Measure the discharge pipe thermistor against Daikin's Check No. 01 chart (disconnect its connector from the PCB and measure the sensor itself): 20 kOhm at 25 C, about 25 kOhm at 20 C, 16.1 kOhm at 30 C, 10.6 kOhm at 40 C and 7.2 kOhm at 50 C (R25 = 20 kOhm, B = 3950 K). A reading far off the chart for the pipe's actual temperature condemns the thermistor; a sensor clipped off the pipe or with a damaged harness reads the air instead of the pipe and produces the same false trip.
  6. Hand a shop this pinpoint: E5 confirmed with the count of restarts it took to lock out, and whether the discharge thermistor was found connected — SM-TS3's inverter detail adds compressor lock, high differential pressure and UVW connection errors to the same code on some models, so the technician will check the compressor connections first if the unit never starts at all

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the E5 code

Typical pro repair $450–$2,000

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

Before you buy: check the discharge pipe thermistor first

Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).

A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.

Test values from manualshelf.com documentation - confirm against your model's own tech sheet.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.

Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes

See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →