Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) U4 Error Code

What the U4 code means

U4 is a signal transmission error between the indoor unit and the outdoor unit — it is detected when the data received over the indoor-outdoor transmission line cannot be received normally or its content is abnormal. It is the most common Daikin ductless code because the link it watches is just the interconnecting cable between the two units: a wiring error, a broken signal wire, a dead board at either end, or the outdoor unit simply having no power all surface as U4. The indoor OPERATION lamp blinking is the visible trigger to pull the code with the remote. The FTXS/FDXS/FTXM/RMXS families share a unified residential ductless table.

Likely causes

  1. Wiring error or broken indoor-to-outdoor connection wires (the No. 3 signal wire is the classic break)
  2. Outdoor unit power supply off (SM-TS3 adds this explicitly)
  3. System address mismatch between units
  4. Defective outdoor unit PCB
  5. Defective indoor unit PCB
  6. Disturbed power supply waveform (noise on the line)

How to fix it — step by step

  1. Read the code out with the remote first (hold TIMER CANCEL for 5 seconds until 00 shows, then press it repeatedly until the long beep — that code is the stored fault) and confirm it is U4 before touching wiring
  2. Turn the breaker off. Check the indoor-to-outdoor interconnecting cable end to end: correct terminals at both units, no breaks, no insulation damage, and the signal wire (terminal 3) firmly landed — a wiring error or a broken No. 3 wire is the first cause to check
  3. Confirm the outdoor unit actually has power: its breaker/disconnect on. SM-TS3 lists 'outdoor unit power supply is OFF' as a U4 cause in its own right
  4. Restore power, wait at least 7 seconds, then check LED A on the outdoor PCB (start a fan operation first to cancel standby power-saving): a blinking LED A means the outdoor board's microcomputer is alive and diagnosing normally; a dark LED points at the outdoor PCB or its supply
  5. If wiring, power and addresses all check out, Daikin's flow checks the power-supply waveform for disturbance (Check No. 11) — find and remove the noise source on the circuit
  6. Remaining documented outcomes, in order: replace the connection wires if suspect, then the indoor PCB; a unit that still cannot exchange data after that has a defective outdoor PCB. Hand a shop this pinpoint: transmission verified, wiring and supply proven, LED A state noted

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the U4 code

Parts run $80–$400Typical pro repair $450–$2,000Fixing it yourself typically saves $50–$1,920

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.