Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) J3 Error Code
What the J3 code means
J3 is a discharge pipe thermistor abnormality — the sensor on the compressor's discharge line is reading out of range (open, shorted or disconnected), as distinct from F3, where the sensor is believed and its temperature is too high. The discharge thermistor is the compressor's primary thermal witness: it feeds the F3 protection, the U0 shortage detection and the E5 overload logic, so one failed sensor can echo into several other codes. It is a low-voltage part, testable against Daikin's standard thermistor chart.
Likely causes
- Thermistor connector disconnected
- Defective discharge pipe thermistor
- Defective outdoor unit PCB
How to fix it — step by step
- Confirm J3 with the remote self-diagnosis, then breaker OFF
- Locate the discharge pipe thermistor on the compressor's discharge line at the outdoor unit. Check its connector is seated — disconnection heads Daikin's thermistor-code causes
- Test it against the resistance chart (Check No. 01 method): about 20 kΩ at 25°C (77°F) at the sensor's actual temperature, roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C. Open, shorted or far off-chart condemns it — replace the discharge pipe thermistor → Shop the discharge pipe thermistor at Amazon
- If the thermistor conforms and is connected, the outdoor PCB is misreading it — the documented remainder; hand a shop the pinpoint with your resistance reading
- Keep J3 distinct from F3: J3 says the discharge sensor itself is faulty; F3 says the (believed) discharge temperature went too high. A bad J3 sensor can cause a false F3, which is why the F3 flow tests thermistors first
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the discharge pipe thermistor.
Shop the discharge pipe thermistor at Amazon
Also tied to this fault: outdoor unit PCB - Shop at Amazon
Parts that commonly fix the J3 code
- discharge pipe thermistor$25–$80Shop at Amazon
- outdoor unit PCB$80–$400Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the discharge pipe thermistor first
Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).
A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.
Test values from manualshelf.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes
See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →