Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) U2 Error Code

What the U2 code means

U2 is a voltage detection fault: the service manual defines it as low-voltage detection or over-voltage detection (the operation manual: 'drop voltage or main circuit overvoltage'; SM-TS3 frames it as a power supply malfunction or instantaneous power failure). Detection happens on both sides — the indoor PCB watches for its zero-cross signal, and the outdoor DC bus voltage falling below roughly 150-200 V (model-dependent) or an over-voltage signal stops the compressor, with an automatic restart after about 3 minutes. U2 after a flicker or outage is usually the protection reporting the event; U2 on a clean supply points into the unit's detection circuits.

Likely causes

  1. Supply voltage not as specified (genuinely low or high mains)
  2. Momentary voltage fall or momentary power failure
  3. Electrical noise / disturbed supply waveform
  4. Compressor harness disconnected
  5. Defective DC voltage detection or over-voltage detection circuit, PAM control, or indoor PCB

How to fix it — step by step

  1. Confirm U2 with the remote self-diagnosis, then check the supply itself — Daikin's first step is to measure the power supply voltage and confirm it is as rated for the unit. A genuinely low or sagging supply (long undersized run, failing service, heavy shared load) is corrected at the supply, not the air conditioner
  2. Consider the documented transients: a momentary voltage fall or momentary power failure sets U2 and the unit auto-restarts after about a 3-minute standby. A U2 that appears once after a storm or outage and never returns was the protection working
  3. Breaker off (leave it off at least 30 seconds before any restart), then check the compressor harness connection — loose or disconnected is a listed cause; reconnect it
  4. Restart and observe: if U2 returns within about 3 minutes with a proven supply and harness, look at disturbance factors — electrical noise and power-supply distortion on the circuit. Note what else shares the circuit; a noise source found and removed is a fix
  5. If supply, transients, harness and noise are all ruled out, the documented remainder is the detection circuitry itself — the DC voltage / over-voltage detection circuits or the indoor PCB. Hand the shop the measured supply voltage and the restart behavior

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the U2 code

Parts run $80–$400Typical pro repair $450–$2,000Fixing it yourself typically saves $50–$1,920

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.