Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) A3 Error Code

What the A3 code means

A3 is a drain level control system abnormality (SM-TS3; the owner manuals phrase it 'drain pump abnormal'). It applies to ductless models fitted with a drain pump and float switch — ceiling and concealed units rather than plain wall mounts: the float switch has detected that condensate water is not leaving at the level it should. Daikin's documented causes are short and physical: drain clogging, an upward-sloped drain run, a defective drain pump, or a defective float switch. Note the FTXS/FDXS pair service manual does not even list A3 — those wall models have no drain pump — so seeing A3 means your model is one of the pump-equipped families covered by the unified table.

Likely causes

  1. Clogged drain line (the first listed cause)
  2. Drain run sloped upward so condensate cannot flow out
  3. Defective drain pump
  4. Defective float switch, or its short-circuit connector

How to fix it — step by step

  1. Confirm A3 with the remote self-diagnosis. On drain-pump models the control stops cooling to prevent an overflow, so treat standing water as urgent: switch the unit off if the drain pan is brimming
  2. Find the condensate drain line's exit (outside, usually near the outdoor unit) and check it is actually draining: a line that drips nothing while the unit cools is clogged or airlocked. Clear the clog from the exit end (wet vacuum or a gentle flush) — drain clogging is the first listed cause
  3. Check the drain run's slope where you can see it: Daikin names an upward slope in the drain as a cause — a sagging or rising section traps water and trips the level control. Re-support the line so it falls continuously to the exit
  4. If drainage is free and correctly sloped, the remaining documented causes are the drain pump and the float switch inside the indoor unit: a pump that never runs (listen for it at start-up) or a float stuck in the raised position. Access is behind the indoor unit's panel/drain pan — pump or float switch replacement is the fix, and it is reasonable to hand this step to a service shop with the drain line already proven clear
  5. After any fix, run the unit in cooling and confirm condensate flows steadily from the drain exit and A3 does not return

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the A3 code

Parts run $10–$60Typical pro repair $450–$2,000Fixing it yourself typically saves $390–$1,990

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.