Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) C9 Error Code
What the C9 code means
C9 is the room temperature thermistor abnormality — the sensor that samples the air entering the indoor unit (the 'room temperature thermistor'; SM-TS3's 'suction air thermistor'). It shares a service-manual section and an identical decision rule with C4: the thermistor input sits outside its valid voltage range during compressor operation, so the circuit is open, shorted, disconnected, or misread by the board. One documentation quirk to know: in the FTXS owner table, C9 is called a 'faulty suction air temperature sensor,' which matches — but the same phrase is printed for H9, defined as the outdoor temperature thermistor. Trust this placement: C9 is indoors, H9 is outdoors.
Likely causes
- Thermistor connector disconnected
- Defective thermistor
- Defective indoor unit PCB
How to fix it — step by step
- Confirm C9 with the remote self-diagnosis, then breaker OFF before opening the indoor unit
- Locate the room temperature (suction air) thermistor: it sits in the intake air path behind the front cover, near the filters, so it can sample return air. Check its connector is fully seated — disconnection is the first listed cause for this code pair
- Test the thermistor against the chart (Check No. 01): about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C, measured at the sensor's actual temperature. Open, shorted or far off-chart condemns the thermistor — replace the room temperature thermistor → Shop the room temperature thermistor at Amazon
- If the thermistor is on-chart and connected, the indoor unit PCB is misreading a good sensor — the documented remainder is the indoor PCB. Hand a shop the pinpoint with the resistance you measured → Shop the indoor unit pcb at Amazon
- After any fix, sanity-check the result: the unit's displayed/sensed room temperature should track a thermometer in the room instead of reading a fixed extreme
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the room temperature thermistor.
Shop the room temperature thermistor at Amazon
Also tied to this fault: indoor unit PCB - Shop at Amazon
Parts that commonly fix the C9 code
- room temperature thermistor$25–$80Shop at Amazon
- indoor unit PCB$80–$400Shop at Amazon
- Tools for this job, if you need them$10–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the room temperature thermistor first
Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).
A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.
Test values from manualshelf.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes
See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →