Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) P3 Error Code

What the P3 code means

P3 is a malfunction of the thermistor in the switch box (SM-TS3) — the temperature sensor inside the outdoor unit's electrical (switch) box reads faulty. It is the sensor counterpart to L3 (the box temperature actually rising): P3 says the reading cannot be trusted. This code belongs to Daikin's unified residential ductless malfunction table (SM-TS3), shared across the FTXS/FDXS/FTXM/RMXS families; pull it with the remote self-diagnosis before acting on it.

Likely causes

  1. Thermistor connector disconnected
  2. Defective switch box thermistor
  3. Defective outdoor unit PCB

How to fix it — step by step

  1. Confirm the code with the remote self-diagnosis first (hold TIMER CANCEL for 5 seconds until 00 shows, then press it repeatedly until the long beep marks the stored code), then breaker OFF
  2. Locate the switch box thermistor in the outdoor control box and check its connector is seated
  3. Test it against Daikin's thermistor chart: about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C, judged at the sensor's actual temperature. Open, shorted or far off-chart condemns the thermistor — replace the switch box thermistor → Shop the switch box thermistor at Amazon
  4. If the thermistor conforms and is connected, the outdoor PCB is misreading it — hand a shop the pinpoint with your resistance reading. Note the L3 pairing: a bad P3 sensor can produce false L3 trips

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the P3 code

Parts run $25–$400Typical pro repair $450–$2,000Fixing it yourself typically saves $50–$1,975

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

Before you buy: check the switch box thermistor first

Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).

A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.

Test values from manualshelf.com documentation - confirm against your model's own tech sheet.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.