Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) J6 Error Code
What the J6 code means
J6 is the outdoor heat exchanger thermistor abnormality — the sensor clipped to the outdoor coil reads out of range. This reading drives defrost decisions in heating and capacity/protection logic year-round, so a failed J6 shows up as strange defrost behavior and outdoor coil icing as much as a stopped unit. Like Daikin's other thermistor codes it is decided electrically (open/short/disconnected vs a misreading board) and is testable against the standard thermistor resistance chart.
Likely causes
- Thermistor connector disconnected
- Defective outdoor heat exchanger thermistor
- Defective outdoor unit PCB
How to fix it — step by step
- Confirm J6 with the remote self-diagnosis, then breaker OFF
- Locate the outdoor heat exchanger thermistor (clipped to the outdoor coil). Check its connector is seated
- Test against the resistance chart (Check No. 01 method): about 20 kΩ at 25°C (77°F) at the coil's actual temperature, roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C. Open, shorted or off-chart condemns the thermistor — replace the outdoor heat exchanger thermistor → Shop the outdoor heat exchanger thermistor at Amazon
- If the sensor conforms and is connected, the outdoor PCB is the documented remainder — hand a shop the pinpoint with the resistance and ambient temperature noted
- Expect knock-on behavior while this sensor is bad: defrosts at wrong times or heavy outdoor-coil frosting in heating, since this reading times the defrost cycle
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the outdoor heat exchanger thermistor.
Shop the outdoor heat exchanger thermistor at Amazon
Also tied to this fault: outdoor unit PCB - Shop at Amazon
Parts that commonly fix the J6 code
- outdoor heat exchanger thermistor$25–$80Shop at Amazon
- outdoor unit PCB$80–$400Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the outdoor heat exchanger thermistor first
Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).
A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.
Test values from manualshelf.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.