Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) P4 Error Code
What the P4 code means
P4 is a radiation fin thermistor abnormality — the sensor that watches the inverter heatsink's temperature is itself faulty (operation manual: 'faulty inverter circuit heatsink temperature sensor'). It is the sensor-fault counterpart to L4, the actual over-temperature event: P4 means the reading cannot be trusted, L4 means the reading is believed and too high. The thermistor is a low-voltage part on the outdoor PCB's heatsink, testable against Daikin's standard resistance chart.
Likely causes
- Defective radiation fin thermistor
- Thermistor connector disconnected
- Defective outdoor unit PCB
How to fix it — step by step
- Confirm P4 with the remote self-diagnosis, then breaker OFF
- Locate the radiation fin thermistor on the inverter heatsink in the outdoor control box and check its connector is seated
- Test it against the thermistor chart (Check No. 01 method: about 20 kΩ at 25°C). Open, shorted or off-chart condemns the fin thermistor — replace it
- If the thermistor conforms and is connected, the outdoor PCB is misreading it — the documented remainder. Hand a shop the pinpoint with the resistance measured
- Keep P4 distinct from L4: P4 says the fin temperature sensor is faulty; L4 says the (believed) fin temperature is too high. A failed P4 sensor can trigger false L4 trips
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the radiation fin thermistor.
Shop the radiation fin thermistor at Amazon
Also tied to this fault: outdoor unit PCB - Shop at Amazon
Parts that commonly fix the P4 code
- radiation fin thermistor$25–$80Shop at Amazon
- outdoor unit PCB$80–$400Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the radiation fin thermistor first
Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).
A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.
Test values from manualshelf.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes
See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →