Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) J7 Error Code
What the J7 code means
J7 is a malfunction of a refrigerant-circuit thermistor — SM-TS3 groups J7/J8 as the liquid pipe (1) thermistors and J9 as the gas pipe thermistor. The sensor reads out of range (open, shorted or disconnected), and because these temperatures feed the control's picture of the refrigerant circuit, the system stops rather than run blind. This code belongs to Daikin's unified residential ductless malfunction table (SM-TS3), shared across the FTXS/FDXS/FTXM/RMXS families; pull it with the remote self-diagnosis before acting on it.
Likely causes
- Thermistor connector disconnected
- Defective liquid pipe thermistor
- Defective outdoor unit PCB
How to fix it — step by step
- Confirm the code with the remote self-diagnosis first (hold TIMER CANCEL for 5 seconds until 00 shows, then press it repeatedly until the long beep marks the stored code), then breaker OFF
- Locate the liquid pipe (1) thermistor on the refrigerant piping at the outdoor unit and check its connector is seated
- Test it against Daikin's thermistor chart: about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C, judged at the sensor's actual temperature. Open, shorted or far off-chart condemns the thermistor — replace the thermistor
- If the thermistor conforms and is connected, the outdoor PCB is misreading it — hand a shop the pinpoint with your resistance reading
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the liquid pipe thermistor.
Shop the liquid pipe thermistor at Amazon
Also tied to this fault: outdoor unit PCB - Shop at Amazon
Parts that commonly fix the J7 code
- liquid pipe thermistor$25–$80Shop at Amazon
- outdoor unit PCB$80–$400Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the liquid pipe thermistor first
Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).
A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.
Test values from manualshelf.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes
See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →