Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) A5 Error Code

What the A5 code means

A5 is the indoor coil protection control: in cooling it is freeze-up protection (the indoor heat exchanger temperature has fallen below 0°C / 32°F), and in heating it is the peak-cut / high-pressure control (indoor heat exchanger above roughly 60-65°C / 140-149°F, model-dependent). Daikin's operation manual phrases it 'high pressure control or freeze-up protector.' Both directions have the same root theme — air is not moving through the indoor coil the way it should — which is why Daikin's documented check order starts with the air passage, the filter and the coil, and only reaches the thermistor and indoor PCB at the end.

Likely causes

  1. Clogged indoor air filter (Daikin's documented check order puts airflow first)
  2. Dust accumulation on the indoor heat exchanger
  3. Short-circuited air — discharge air looping straight back into the intake
  4. Defective indoor heat exchanger thermistor
  5. Defective indoor unit PCB

How to fix it — step by step

  1. Confirm A5 with the remote self-diagnosis, then work the check order, airflow first, parts last
  2. Check the air passage around the indoor unit: is discharge air short-circuiting straight back into the intake (unit boxed in, obstruction tight against the outlet)? Give the unit a clear passage
  3. Clean the air filters. A clogged filter is a named cause in both modes — wash or vacuum the filters and refit them dry
  4. Clean dust off the indoor heat exchanger behind the filters (soft brush / vacuum). A dust-blanketed coil freezes in cooling and overheats in heating exactly like a dirty filter does
  5. Run the unit and watch: if A5 clears and stays away through a full cycle, airflow was the fault — no parts needed
  6. If A5 returns with clean filters, a clean coil and clear passage, the remaining documented causes are the indoor heat exchanger thermistor and the indoor PCB: the thermistor is tested against Daikin's resistance chart (Check No. 01 — about 20 kΩ at 25°C); a thermistor off the chart is replaced, and a thermistor that conforms leaves the indoor PCB as the documented replacement → Shop the indoor heat exchanger thermistor at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the A5 code

Parts run $5–$400Typical pro repair $450–$2,000Fixing it yourself typically saves $50–$1,995

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

Before you buy: check the indoor heat exchanger thermistor first

Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).

A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.

Test values from manualshelf.com documentation - confirm against your model's own tech sheet.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.

Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes

See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →