Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) U0 Error Code

What the U0 code means

U0 means refrigerant shortage. It is detected indirectly — from compressor current, discharge pipe temperature and expansion valve behavior, or a collapsed temperature difference across the system — because these ductless units carry no pressure gauge ports for a quick reading. In practice U0 almost always means the charge has leaked out somewhere, though a closed stop valve, a disconnected thermistor faking the readings, or a failed expansion valve can produce the same detection. Refrigerant work is licensed, sealed-system work: confirm the code and the non-refrigerant causes, and the pinpoint for the technician is leak-find, repair, then recharge with the specified amount.

Likely causes

  1. Refrigerant shortage from leakage (the headline cause)
  2. Stop valve closed after installation or service
  3. A disconnected thermistor (discharge pipe, indoor or outdoor heat exchanger, room or outdoor temperature) making the control misread the system
  4. Defective electronic expansion valve
  5. Poor compressor compression performance

How to fix it — step by step

  1. Confirm U0 with the remote self-diagnosis (TIMER CANCEL hold, cycle to the long beep). U0 is a protection detection, not a parts verdict — Daikin detects it three ways (low input current for compressor frequency, discharge temperature vs expansion valve behavior, or a too-small suction/discharge temperature difference)
  2. Breaker off, then Check No. 01 from the service manual: verify no thermistor is disconnected — discharge pipe, indoor and outdoor heat exchanger, room and outdoor air thermistors all plugged in — and that their resistances are normal. A disconnected thermistor can fake this code
  3. Check the stop valves on the outdoor unit: a closed stop valve (left shut after install or service) is a documented cause — open it fully if found closed
  4. Look for the leak evidence Daikin names: oil oozing at flare connections and piping joints inside either unit. Oil at a flare means refrigerant has been leaving there — that joint gets repaired or re-flared, and cracked piping replaced, before any recharge
  5. Beyond this point it is sealed-system work: the technician verifies the electronic expansion valve (Check No. 12), then checks for refrigerant shortage and recharges with the specified amount of fresh refrigerant after leak repair. Recharging without finding the leak only buys time until U0 returns
  6. If U0 persists with correct charge and good thermistors, the documented tail is the compressor's compression performance and the outdoor PCB — hand the shop the checks already done

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the U0 code

Typical pro repair $800–$3,000

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.