Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) CA Error Code

What the CA code means

CA is a malfunction of the discharge air thermistor (SM-TS3) — the sensor that measures the air temperature leaving the indoor unit. It is one of Daikin's thermistor family: the circuit is open, shorted or disconnected, or the board misreads it. This code belongs to Daikin's unified residential ductless malfunction table (SM-TS3), shared across the FTXS/FDXS/FTXM/RMXS families; pull it with the remote self-diagnosis before acting on it.

Likely causes

  1. Thermistor connector disconnected
  2. Defective discharge air thermistor
  3. Defective indoor unit PCB

How to fix it — step by step

  1. Confirm the code with the remote self-diagnosis first (hold TIMER CANCEL for 5 seconds until 00 shows, then press it repeatedly until the long beep marks the stored code), then breaker OFF before opening the indoor unit
  2. Locate the discharge air thermistor in the indoor unit's outlet air path and check its connector is seated
  3. Test it against Daikin's thermistor chart: about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C at the sensor's actual temperature. Open, shorted or off-chart condemns the thermistor — replace it
  4. If the thermistor conforms and is connected, the indoor PCB is the documented remainder — hand a shop the pinpoint with your resistance reading

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the CA code

Parts run $25–$400Typical pro repair $450–$2,000Fixing it yourself typically saves $50–$1,975

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

Before you buy: check the discharge air thermistor first

Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).

A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.

Test values from manualshelf.com documentation - confirm against your model's own tech sheet.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.