Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) J5 Error Code
What the J5 code means
J5 is a malfunction of the suction pipe thermistor (SM-TS3) — the sensor on the suction line reads out of range. Suction temperature feeds superheat and compressor protection logic, so a failed J5 distorts metering decisions even while the system still runs. This code belongs to Daikin's unified residential ductless malfunction table (SM-TS3), shared across the FTXS/FDXS/FTXM/RMXS families; pull it with the remote self-diagnosis before acting on it.
Likely causes
- Thermistor connector disconnected
- Defective suction pipe thermistor
- Defective outdoor unit PCB
How to fix it — step by step
- Confirm the code with the remote self-diagnosis first (hold TIMER CANCEL for 5 seconds until 00 shows, then press it repeatedly until the long beep marks the stored code), then breaker OFF
- Locate the suction pipe thermistor on the suction line at the outdoor unit and check its connector is seated
- Test it against Daikin's thermistor chart: about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C, judged at the sensor's actual temperature. Open, shorted or far off-chart condemns the thermistor — replace the suction pipe thermistor → Shop the suction pipe thermistor at Amazon
- If the thermistor conforms and is connected, the outdoor PCB is misreading it — hand a shop the pinpoint with the resistance and the pipe temperature it was measured at
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the suction pipe thermistor.
Shop the suction pipe thermistor at Amazon
Also tied to this fault: outdoor unit PCB - Shop at Amazon
Parts that commonly fix the J5 code
- suction pipe thermistor$25–$80Shop at Amazon
- outdoor unit PCB$80–$400Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the suction pipe thermistor first
Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).
A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.
Test values from manualshelf.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.