Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) C4 Error Code
What the C4 code means
C4 is an indoor heat exchanger thermistor abnormality. The service manual decides it electrically: during compressor operation the thermistor's input voltage sits outside its valid range (above about 4.96 V or below 0.04 V), meaning the sensor circuit is open, shorted, or the board is misreading it. SM-TS3 words the same code as a malfunction of the liquid pipe thermistor for the heat exchanger. The thermistor itself is clipped to the indoor coil and is a low-voltage, owner-replaceable part once the unit is powered down — this is one of the few Daikin codes with a fully documented home test, the resistance chart.
Likely causes
- Thermistor connector disconnected
- Defective thermistor
- Defective indoor unit PCB
How to fix it — step by step
- Confirm C4 with the remote self-diagnosis, then breaker OFF before opening the indoor unit — the thermistor is a low-voltage part, but the unit must be dead while panels are off
- Locate the indoor heat exchanger thermistor: clipped to the indoor coil behind the front panel and filters. Check its connector first — a disconnected connector is the first listed cause. Reseat it firmly
- Test the thermistor against the chart (Check No. 01): resistance should be about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C. A thermistor that reads open, shorted, or far off the chart for the coil's actual temperature is condemned — replace the indoor heat exchanger thermistor
- If the thermistor conforms to the chart and the connector is sound, the documented remainder is the indoor unit PCB (it is misreading a good sensor) — replace it, or hand a shop the pinpoint: C4 confirmed, thermistor resistance measured on-chart, connector verified → Shop the indoor unit pcb at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the indoor heat exchanger thermistor.
Shop the indoor heat exchanger thermistor at Amazon
Also tied to this fault: indoor unit PCB - Shop at Amazon
Parts that commonly fix the C4 code
- indoor heat exchanger thermistor$25–$80Shop at Amazon
- indoor unit PCB$80–$400Shop at Amazon
- Tools for this job, if you need them$15–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
Before you buy: check the indoor heat exchanger thermistor first
Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).
A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.
Test values from manualshelf.com documentation - confirm against your model's own tech sheet.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.