Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) C4 Error Code

What the C4 code means

C4 is an indoor heat exchanger thermistor abnormality. The service manual decides it electrically: during compressor operation the thermistor's input voltage sits outside its valid range (above about 4.96 V or below 0.04 V), meaning the sensor circuit is open, shorted, or the board is misreading it. SM-TS3 words the same code as a malfunction of the liquid pipe thermistor for the heat exchanger. The thermistor itself is clipped to the indoor coil and is a low-voltage, owner-replaceable part once the unit is powered down — this is one of the few Daikin codes with a fully documented home test, the resistance chart.

Likely causes

  1. Thermistor connector disconnected
  2. Defective thermistor
  3. Defective indoor unit PCB

How to fix it — step by step

  1. Confirm C4 with the remote self-diagnosis, then breaker OFF before opening the indoor unit — the thermistor is a low-voltage part, but the unit must be dead while panels are off
  2. Locate the indoor heat exchanger thermistor: clipped to the indoor coil behind the front panel and filters. Check its connector first — a disconnected connector is the first listed cause. Reseat it firmly
  3. Test the thermistor against the chart (Check No. 01): resistance should be about 20 kΩ at 25°C (77°F), roughly 65.9 kΩ at 0°C and 16.1 kΩ at 30°C. A thermistor that reads open, shorted, or far off the chart for the coil's actual temperature is condemned — replace the indoor heat exchanger thermistor
  4. If the thermistor conforms to the chart and the connector is sound, the documented remainder is the indoor unit PCB (it is misreading a good sensor) — replace it, or hand a shop the pinpoint: C4 confirmed, thermistor resistance measured on-chart, connector verified → Shop the indoor unit pcb at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix the C4 code

Parts run $25–$400Typical pro repair $450–$2,000Fixing it yourself typically saves $50–$1,975
  • indoor heat exchanger thermistor$25–$80Shop at Amazon
  • indoor unit PCB$80–$400Shop at Amazon
  • Tools for this job, if you need them$15–$65

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

Before you buy: check the indoor heat exchanger thermistor first

Test: Disconnect the thermistor's connector from the PCB and measure its resistance at the sensor's actual temperature (Daikin service manual SiUS091133, Check No. 01).

A good one reads: About 20 kΩ at 25 °C (77 °F); 25 kΩ at 20 °C; 16.1 kΩ at 30 °C; 65.9 kΩ at 0 °C; 10.6 kΩ at 40 °C. Open, shorted or far off the chart means the thermistor has failed.

Test values from manualshelf.com documentation - confirm against your model's own tech sheet.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.

Related Daikin Air Conditioner Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) error codes

See all Daikin Ductless Mini-Split (FTXS / FDXS / FTXM / RMXS) codes & guides →