York Affinity, Echelon, Acclimate Heat Pump Series Common Problems
Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 21 problems covered.
Not sure of the code? Tap along with it
If your York Heat pump blinks or beeps a pattern instead of showing a code, tap the button in time with each blink or beep. A pause longer than a second and a half starts a new group - we will match the rhythm to a code.
Your taps: -
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
| Problem | What it means | Check first | |
|---|---|---|---|
| 1 flash (LED1 red), LED2 (green) on | Table 7 (Wiring Related Fault Codes) of the YorkGuard VI instructions displays wiring faults by flashing LED1… | Contactor wired to the wrong compressor output terminal (M, M1 or M2) | › |
| 1 flash (LED1 red), LED2 off | In Table 5 of the YorkGuard VI instructions (501062-UAI-A-0909), one red flash on LED1 with LED2 off is… | Outdoor coil dirty or airflow blocked in cooling | › |
| 2 flashes (LED1 red), LED2 (green) on | Two red flashes on LED1 with LED2 on is 'Y2 present without Y1' in Table 7 of the YorkGuard VI instructions… | Y1 conductor broken, loose or not landed at the thermostat or control | › |
| 2 flashes (LED1 red), LED2 off | Table 5 of the YorkGuard VI instructions lists two red flashes on LED1 with LED2 off as 'High-pressure switch… | Refrigerant overcharge raising discharge pressure | › |
| 3 flashes (LED1 red), LED2 (green) on | Three red flashes on LED1 with LED2 on is 'Y1 and W present without Y2 in two stage mode' in Table 7 of the… | Thermostat misconfigured for the system's staging or heat type | › |
| 3 flashes (LED1 red), LED2 off | Three red flashes on LED1 with LED2 off is, in Table 5 of the YorkGuard VI instructions, 'High-pressure… | Indoor airflow too low during defrost (dirty filter or weak blower) | › |
| 4 flashes (LED1 red), LED2 off | Table 5 of the YorkGuard VI instructions lists four red flashes on LED1 with LED2 off as 'Low-pressure switch… | Refrigerant leak or undercharge (loss of charge switch opening) | › |
| 5 flashes (LED1 red), LED2 off | Five red flashes on LED1 with LED2 off is 'Low Voltage (less than 19 VAC) preventing further relay outputs'… | Undersized or failing control transformer | › |
| 6 flashes (LED1 red), LED2 off | Six red flashes on LED1 with LED2 off is 'Low Voltage (less than 16 VAC) stopped current relay outputs' in… | Failing or overloaded control transformer | › |
| 7 flashes (LED1 red), LED2 off | Seven red flashes on LED1 with LED2 off is the last row of Table 5 in the YorkGuard VI instructions: 'Pipe… | Liquid line or ambient sensor reading incorrectly, corrupting the protection timing | › |
| 8 flashes (LED1 red), LED2 (green) on | Eight red flashes on LED1 with LED2 on is 'Defrost Curve Jumper Error (Invalid jumper setting preventing… | Defrost curve jumper missing after service | › |
| LED1 (red) on, LED2 (green) 1 flash | Table 6 (Sensor or Switch Fault Codes) of the YorkGuard VI instructions displays sensor faults by energizing… | Ambient sensor shorted internally | › |
| LED1 (red) on, LED2 (green) 2 flashes | Two green flashes on LED2 with LED1 held on is 'Outdoor ambient sensor failure (open)' in Table 6 of the… | Ambient sensor failed open | › |
| LED1 (red) on, LED2 (green) 3 flashes | Three green flashes on LED2 with LED1 on is 'Liquid line sensor failure (short)' in Table 6 of the YorkGuard… | Liquid line sensor shorted internally | › |
| LED1 (red) on, LED2 (green) 4 flashes | Four green flashes on LED2 with LED1 on is 'Liquid line sensor failure (open)' in Table 6 of the YorkGuard VI… | Liquid line sensor failed open | › |
| LED1 (red) on, LED2 (green) 5 flashes | Five green flashes on LED2 with LED1 on is 'High discharge line temperature' in Table 6 of the YorkGuard VI… | Low refrigerant charge overheating the compressor | › |
| LED1 (red) on, LED2 (green) 6 flashes | Six green flashes on LED2 with LED1 on is 'Low discharge line temperature' in Table 6 of the YorkGuard VI… | Discharge sensor loose or off the line, reading ambient instead | › |
| LED1 (red) on, LED2 (green) 7 flashes | Seven green flashes on LED2 with LED1 on is 'Discharge line sensor failure (short)' in Table 6 of the… | Discharge sensor shorted internally | › |
| LED1 (red) on, LED2 (green) 8 flashes | Eight green flashes on LED2 with LED1 on is 'Bonnet sensor failure (short)' in Table 6 of the YorkGuard VI… | Bonnet sensor shorted internally | › |
| LED1 (red) on, LED2 (green) 9 flashes | Nine green flashes on LED2 with LED1 on is the last row of Table 6 in the YorkGuard VI instructions: 'Fossil… | FFUEL jumper left in OFF position on a dual-fuel install | › |
| LED1 (red) on, LED2 (green) off | Table 5 (Operational Fault Codes) of Johnson Controls document 501062-UAI-A-0909, for the YorkGuard VI demand… | Internal failure of the demand defrost control board | › |
All York heat pump models & codes →
Once you know the part you need, browse York Affinity, Echelon, Acclimate Heat Pump Series replacement parts → The parts shelves are organized by brand, with the parts that actually fix these codes.