York Heat pump Affinity, Echelon, Acclimate Heat Pump Series LED1 (red) on, LED2 (green) 6 flashes

What it should look like on your machine

then it repeats

6 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Six green flashes on LED2 with LED1 on is 'Low discharge line temperature' in Table 6 of the YorkGuard VI instructions, under Optional Discharge Line Sensor Faults, X/L output 2 flashes (soft) or 3 (hard). It applies only to units with the optional discharge line sensor fitted. A discharge line that stays too cool while the compressor runs means the compressor is not doing normal work: liquid refrigerant flooding back, a compressor not pumping effectively, or a sensor that has lost contact with the line can all produce it. The control flags it because the same sensor is trusted for high-temperature protection, and a sensor or compressor problem at the low end undermines that protection.

Likely causes

  1. Discharge sensor loose or off the line, reading ambient instead
  2. Liquid floodback from overcharge or a failed metering device
  3. Compressor not pumping effectively
  4. Sensor or wiring fault reading low

How to fix it — step by step

  1. Record the pattern (LED1 on, LED2 six flashes) and note whether the compressor was actually running and heating or cooling when it set.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Remove the control-box panel and check the discharge sensor is clipped tightly to the discharge line with its leads intact to the defrost control; a sensor hanging loose reads air temperature, not line temperature.
  4. Measure the real discharge line temperature with a clamp probe during a run and compare it with the sensor's resistance reading; a hot line with a low reading condemns the sensor or its mounting, while a genuinely cool discharge line sends a technician to pressures, charge and compressor pumping checks.
  5. Re-seat or replace the thermistor if it is the fault; floodback, charge and compressor causes are EPA-certified-technician work. Confirm a normal run with no returning code. → Shop the thermistor at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $25–$80
  • Thermistor$25–$80Shop at Amazon
  • Tools for this job, if you need them$15–$65

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.