York Heat pump Affinity, Echelon, Acclimate Heat Pump Series 1 flash (LED1 red), LED2 off
What it should look like on your machine
then it repeats
1 flash - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
In Table 5 of the YorkGuard VI instructions (501062-UAI-A-0909), one red flash on LED1 with LED2 off is 'High-pressure switch fault (not in lockout yet)', and its X/L output is off. Operational faults are displayed by flashing LED1 red only, with LED2 not energized, and the code repeats after a two-second pause. This is the first pressure trip: the control de-energized the compressor when the switch opened, and if the switch closes and a call remains, it applies the five-minute anti-short-cycle delay and restarts. A single flash therefore means find the pressure cause now, before repeat trips inside six hours turn it into a lockout.
Likely causes
- Outdoor coil dirty or airflow blocked in cooling
- Outdoor fan not running or weak
- Indoor airflow restricted in heating, including a clogged filter
- Refrigerant overcharge
- Failing high pressure switch
How to fix it — step by step
- Record the one-flash code and the operating mode before cycling power, and note whether the outdoor fan was running.
- Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
- Inspect both coils and the indoor filter, then remove the control-box panel to reach the demand defrost control and the pressure switch connections.
- Have a technician connect gauges and watch discharge pressure on a run: pressure climbing to the switch trip with a clean coil and running fan points to overcharge or restriction, while normal pressure at the moment of trip condemns the pressure switch or its wiring.
- Correct the airflow, fan or switch cause, or have charge corrected; Any refrigerant-side repair, charge adjustment or sealed-system work is EPA-certified-technician work only; do not open the refrigerant circuit yourself. Run a full cycle and confirm no second trip occurs.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Outdoor fan motor.
Shop the Outdoor fan motor at Amazon
Also tied to this fault: Air filter - Shop at Amazon
Parts that commonly fix it
- Outdoor fan motorShop at Amazon
- Air filter$5–$30Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related York Heat pump Affinity, Echelon, Acclimate Heat Pump Series problems
- 2 flashes (LED1 red), LED2 (green) on
- 2 flashes (LED1 red), LED2 off
- 3 flashes (LED1 red), LED2 (green) on
- 3 flashes (LED1 red), LED2 off
- 4 flashes (LED1 red), LED2 off
- 5 flashes (LED1 red), LED2 off
- 6 flashes (LED1 red), LED2 off
- 7 flashes (LED1 red), LED2 off
- 8 flashes (LED1 red), LED2 (green) on
- LED1 (red) on, LED2 (green) 1 flash
- LED1 (red) on, LED2 (green) 2 flashes
- LED1 (red) on, LED2 (green) 3 flashes
See all York Affinity, Echelon, Acclimate Heat Pump Series codes & guides →