York Heat pump Affinity, Echelon, Acclimate Heat Pump Series 2 flashes (LED1 red), LED2 (green) on
What it should look like on your machine
then it repeats
2 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Two red flashes on LED1 with LED2 on is 'Y2 present without Y1' in Table 7 of the YorkGuard VI instructions, X/L off. The control is receiving a second-stage compressor call (Y2) with no first-stage call (Y1), which is not a valid thermostat signal sequence for a two-stage system: staging must come up through Y1 first. The manual says wiring faults like this typically occur when the heat pump is first installed or when a component such as the room thermostat or indoor unit is replaced or rewired, so the cause is in the low-voltage wiring or thermostat configuration, not in the compressor or the outdoor board's power section.
Likely causes
- Y1 conductor broken, loose or not landed at the thermostat or control
- Thermostat configured for the wrong staging or a failed Y1 output
- Y1 and Y2 conductors swapped or shorted in the cable
- Indoor unit rewired incorrectly during a replacement
How to fix it — step by step
- Record the pattern (LED1 two flashes, LED2 on) and note any recent thermostat, air handler or control replacement, which the manual names as the usual setting for this fault.
- Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
- At the outdoor control, check the Y1 and Y2 terminals for landed, undamaged conductors, then follow the same check at the indoor unit and thermostat connections.
- With a meter, call for first-stage operation at the thermostat and confirm 24V appears on Y1 at the control, then on Y2 for second stage: Y2 live with Y1 dead proves the break, swap or thermostat output fault the code describes, and the location where Y1 disappears is the fault.
- Repair or re-land the Y1 conductor, correct the thermostat staging configuration, and confirm Y1 then Y2 energize in sequence on a rising call.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the Control board.
Parts that commonly fix it
- Control boardShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related York Heat pump Affinity, Echelon, Acclimate Heat Pump Series problems
- 2 flashes (LED1 red), LED2 off
- 3 flashes (LED1 red), LED2 (green) on
- 3 flashes (LED1 red), LED2 off
- 4 flashes (LED1 red), LED2 off
- 5 flashes (LED1 red), LED2 off
- 6 flashes (LED1 red), LED2 off
- 7 flashes (LED1 red), LED2 off
- 8 flashes (LED1 red), LED2 (green) on
- LED1 (red) on, LED2 (green) 1 flash
- LED1 (red) on, LED2 (green) 2 flashes
- LED1 (red) on, LED2 (green) 3 flashes
- LED1 (red) on, LED2 (green) 4 flashes
See all York Affinity, Echelon, Acclimate Heat Pump Series codes & guides →