York Heat pump Affinity, Echelon, Acclimate Heat Pump Series 8 flashes (LED1 red), LED2 (green) on

What it should look like on your machine

then it repeats

8 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Eight red flashes on LED1 with LED2 on is 'Defrost Curve Jumper Error (Invalid jumper setting preventing compressor operation)' in Table 7 of the YorkGuard VI instructions, X/L off. The demand defrost control selects its defrost curve, the ambient/liquid temperature relationship it uses to start defrost, from a jumper, and some positions are invalid for the model or unused: the related Johnson Controls installation manual for YHJF-family units states position 4 is not used and the control will not allow the compressor to operate with the jumper there, and likewise not if the jumper is in an undescribed position or missing. The unit is therefore stopped by configuration, not by a failed component.

Likely causes

  1. Defrost curve jumper missing after service
  2. Jumper in an invalid or unused position for the model
  3. Jumper moved during a control replacement and not restored
  4. Control replaced and the curve not set for the specific model

How to fix it — step by step

  1. Record the pattern (LED1 eight flashes, LED2 on) before touching the jumper, and photograph its as-found position.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Remove the control-box panel and locate the defrost curve selection jumper on the demand defrost control; compare its position with the model's required curve in the unit's installation manual table.
  4. The control only reads the jumper when the Y and W thermostat inputs are de-energized, per the Johnson Controls manual, so set the thermostat to OFF, place the jumper on the correct numbered position for the model, then restore power and confirm the control accepts it.
  5. Run a heating call and force a defrost with the TEST pins to confirm the compressor operates and the displayed defrost curve matches the jumper, then clear stored faults with the LAST ERROR procedure.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.