York Heat pump Affinity, Echelon, Acclimate Heat Pump Series LED1 (red) on, LED2 (green) 9 flashes

What it should look like on your machine

then it repeats

9 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Nine green flashes on LED2 with LED1 on is the last row of Table 6 in the YorkGuard VI instructions: 'Fossil Fuel Mode setting error (FFUEL jumper in OFF position but bonnet sensor present)', with X/L off. This is a configuration contradiction the control can detect electrically: a bonnet sensor is wired in, which only makes sense for a fossil-fuel (dual-fuel) application, but the FFUEL jumper tells the control fossil fuel mode is off. The compressor is not at fault; the control is refusing to run a configuration that does not agree with itself. It typically appears at installation or after a control board or indoor unit change, exactly the situation the manual says produces sensor and wiring faults.

Likely causes

  1. FFUEL jumper left in OFF position on a dual-fuel install
  2. Bonnet sensor wired in on a system that is not dual-fuel
  3. Replacement control fitted without transferring the original jumper settings
  4. Bonnet sensor circuit shorted so the control thinks a sensor is present

How to fix it — step by step

  1. Record the pattern (LED1 on, LED2 nine flashes) before changing anything, and photograph the control's jumper positions as found.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Remove the control-box panel and locate the FFUEL jumper and the bonnet sensor terminals on the demand defrost control; establish from the indoor unit whether this is truly a dual-fuel system.
  4. Match the hardware to the application: a dual-fuel system needs the bonnet sensor connected and FFUEL set accordingly, while a non-dual-fuel system should have no bonnet sensor input; if no sensor is fitted but the control sees one, test that circuit for a short.
  5. Correct the jumper or wiring to match the actual system, cycle power, and confirm the code clears and both heat pump and auxiliary heat operate as configured.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.