York Heat pump Affinity, Echelon, Acclimate Heat Pump Series 3 flashes (LED1 red), LED2 (green) on
What it should look like on your machine
then it repeats
3 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Three red flashes on LED1 with LED2 on is 'Y1 and W present without Y2 in two stage mode' in Table 7 of the York YZE installation manual (035-20401-001), the same YorkGuard control chart reproduced in 501062-UAI-A-0909. The control sees a first-stage compressor call (Y1) together with a W auxiliary/emergency heat call, but no Y2 second-stage call, in a two-stage system where a genuine high-demand call should stage up through Y2 before bringing on W. That signal combination indicates the thermostat or indoor wiring is producing an impossible staging sequence, so the control flags the wiring/configuration rather than running the system on contradictory commands.
Likely causes
- Thermostat misconfigured for the system's staging or heat type
- W conductor landed or shorted so it energizes with Y1
- Y2 conductor broken or not landed, so second stage never arrives
- Indoor unit or thermostat replaced and rewired incorrectly
How to fix it — step by step
- Record the pattern (LED1 three flashes, LED2 on) before changing wiring, and note any recent thermostat or indoor unit work.
- Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
- Remove the control-box panel and verify the Y1, Y2 and W conductors at the defrost control against the wiring diagram, then check the same terminals at the indoor unit.
- Stage a call at the thermostat and measure each terminal: a correct sequence energizes Y1, then Y2, then W only on a deep or auxiliary call; W voltage arriving with Y1 while Y2 stays dead localizes the fault to the thermostat configuration, a shorted cable or the missing Y2 connection.
- Correct the configuration or wiring proven by the test, then run the full staging sequence again and confirm the code stays clear.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the likely broken part is the Control board.
Parts that commonly fix it
- Control boardShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related York Heat pump Affinity, Echelon, Acclimate Heat Pump Series problems
- 3 flashes (LED1 red), LED2 off
- 4 flashes (LED1 red), LED2 off
- 5 flashes (LED1 red), LED2 off
- 6 flashes (LED1 red), LED2 off
- 7 flashes (LED1 red), LED2 off
- 8 flashes (LED1 red), LED2 (green) on
- LED1 (red) on, LED2 (green) 1 flash
- LED1 (red) on, LED2 (green) 2 flashes
- LED1 (red) on, LED2 (green) 3 flashes
- LED1 (red) on, LED2 (green) 4 flashes
- LED1 (red) on, LED2 (green) 5 flashes
- LED1 (red) on, LED2 (green) 6 flashes
See all York Affinity, Echelon, Acclimate Heat Pump Series codes & guides →