York Heat pump Affinity, Echelon, Acclimate Heat Pump Series LED1 (red) on, LED2 (green) 2 flashes

What it should look like on your machine

then it repeats

2 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Two green flashes on LED2 with LED1 held on is 'Outdoor ambient sensor failure (open)' in Table 6 of the YorkGuard VI instructions, X/L output 2 flashes (soft). An open sensor or broken lead reads as infinite resistance, which the demand defrost control interprets as an out-of-range temperature and rejects, because defrost decisions compare outdoor ambient temperature with liquid line temperature. The manual groups this with the required sensor faults, meaning the control expects this sensor to be present and valid; a missing, unplugged or broken-wire sensor after service is just as likely as a failed sensor element itself.

Likely causes

  1. Ambient sensor failed open
  2. Sensor unplugged or broken lead wire
  3. Corroded connector opening the circuit
  4. Sensor missing after service

How to fix it — step by step

  1. Record the pattern (LED1 on, LED2 two flashes) before power-cycling, and recall the code later with the LAST ERROR button if it clears.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Remove the control-box panel and check that the ambient sensor is actually plugged into the defrost control and that its leads are intact along their whole run.
  4. Measure the sensor's resistance at the control plug: infinite resistance with the sensor connected means an open sensor or lead, and measuring the sensor alone at its own connector separates a bad thermistor from a broken harness. → Shop the thermistor at Amazon
  5. Replace a proven-open thermistor or repair the lead, seat the connector fully, and confirm normal status display and a correct defrost cycle.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related York Heat pump Affinity, Echelon, Acclimate Heat Pump Series problems

See all York Affinity, Echelon, Acclimate Heat Pump Series codes & guides →