York Heat pump Affinity, Echelon, Acclimate Heat Pump Series 6 flashes (LED1 red), LED2 off
What it should look like on your machine
then it repeats
6 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
Six red flashes on LED1 with LED2 off is 'Low Voltage (less than 16 VAC) stopped current relay outputs' in Table 5 of the YorkGuard VI instructions, X/L off. This is the deeper of the control's two low-voltage thresholds: the manual states that if the secondary drops below approximately 16 VAC, the control immediately de-energizes the relay outputs and will not energize any relays until the voltage level increases. Unlike the 19 VAC code, which only blocks new outputs, this one kills running outputs too, so the compressor and fan stop outright. The control stores and displays the fault so a brownout or failing transformer is not mistaken for a failed compressor or board.
Likely causes
- Failing or overloaded control transformer
- Serious low-voltage wiring fault or partial short
- Utility brownout or low line voltage
- Contactor coil drawing excessive current and sagging the secondary
How to fix it — step by step
- Record the six-flash code and note whether the whole system, including the indoor unit and thermostat, shows power problems at the same time.
- Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
- Remove the control-box panel and measure the 24V secondary at the defrost control's R and C terminals; also inspect the contactor coil wiring, since the contactor is the biggest low-voltage load outdoors.
- Compare idle and loaded secondary voltage against the manual's approximately 16 VAC threshold: voltage that collapses only when the contactor energizes points to the coil or transformer capacity, while voltage low everywhere points to the transformer or line supply. → Shop the contactor at Amazon
- Replace a proven-bad contactor coil/contactor or transformer, repair the wiring fault, and confirm outputs stay energized through a full call before clearing the stored code with the LAST ERROR button procedure.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Contactor.
Also tied to this fault: Control board - Shop at Amazon
Parts that commonly fix it
- Contactor$10–$35Shop at Amazon
- Control boardShop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.
Related York Heat pump Affinity, Echelon, Acclimate Heat Pump Series problems
- 7 flashes (LED1 red), LED2 off
- 8 flashes (LED1 red), LED2 (green) on
- LED1 (red) on, LED2 (green) 1 flash
- LED1 (red) on, LED2 (green) 2 flashes
- LED1 (red) on, LED2 (green) 3 flashes
- LED1 (red) on, LED2 (green) 4 flashes
- LED1 (red) on, LED2 (green) 5 flashes
- LED1 (red) on, LED2 (green) 6 flashes
- LED1 (red) on, LED2 (green) 7 flashes
- LED1 (red) on, LED2 (green) 8 flashes
- LED1 (red) on, LED2 (green) 9 flashes
- LED1 (red) on, LED2 (green) off
See all York Affinity, Echelon, Acclimate Heat Pump Series codes & guides →