Lennox Heat pump Common Problems
Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 20 problems covered.
Finding your model number: it is on the outdoor unit's rating plate.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
ML14XP1 (defrost control LEDs)
Two LEDs on the CMC1 defrost control - DS2 (green) and DS1 (red) - combine into the fault and lockout patterns.
| Problem | What it means | Check first | |
|---|---|---|---|
| Green LED (DS2) off, red LED (DS1) on | Table 3 of the ML14XP1 instructions lists green off with red on, under Fault and Lockout Codes, as a low… | Refrigerant leak or undercharge severe enough to trip the switch repeatedly | › |
| Green LED (DS2) off, red LED (DS1) slow flash | On the ML14XP1 defrost control (CMC1), Table 3 of the Lennox installation instructions lists this DS2/DS1… | Low refrigerant charge or a refrigerant leak | › |
| Green LED (DS2) on, red LED (DS1) off | Table 3 of the ML14XP1 instructions lists green on with red off as a high pressure switch lockout. The manual… | Outdoor fan motor failed or its capacitor weak, so the coil cannot shed heat | › |
| Green LED (DS2) slow flash, red LED (DS1) off | On the ML14XP1 defrost control (CMC1), Table 3 lists green slow flash with red off under Fault and Lockout… | Outdoor fan not running or running weakly in cooling | › |
XP17 (Alert codes)
Communicating-system Alert codes in the 400 series, shown at the control and thermostat.
| Problem | What it means | Check first | |
|---|---|---|---|
| Alert 400 | The XP17 installation instructions (506586-01), Table 15, pair iComfort Touch thermostat Alert Code 400 with… | Compressor internal overload open from high head pressure | › |
| Alert 402 | Table 15 of the XP17 instructions pairs Alert Code 402 with 'System pressure trip'. Lennox's text says it… | High head pressure from refrigerant overcharge | › |
| Alert 404 | Alert Code 404 in XP17 Table 15 is 'Locked rotor', a critical alert. Lennox describes the compressor as… | Failed or shorted run capacitor | › |
| Alert 405 | Alert Code 405 in XP17 Table 15 is 'Open circuit', a critical alert: the compressor has an open circuit due… | Outdoor disconnect open or breaker/fuse open | › |
| Alert 406 | Alert Code 406 in XP17 Table 15 is 'Open start circuit', a critical alert: current is not sensed by the start… | Failed run capacitor | › |
| Alert 407 | Alert Code 407 in XP17 Table 15 is 'Open run circuit', a critical alert: current is not sensed by the run… | Open run wiring or loose connector at the compressor R terminal | › |
| Alert 408 | Alert Code 408 in XP17 Table 15 is 'Welded contactor', a critical alert: the compressor always runs. Lennox… | Contactor contacts welded or fused shut | › |
| Alert 409 | Alert Code 409 in XP17 Table 15 is 'Secondary low voltage': the 24VAC secondary is below 18VAC. Lennox lists… | Control transformer overloaded by connected accessories or a partial short | › |
| Alert 410 | In the XP17 fault and lockout table (Table 14 in 506586-01), Alert Code 410 is 'Low pressure fault', a… | Restricted airflow over indoor or outdoor coil | › |
| Alert 411 | Alert Code 411 in the XP17 table is 'Low pressure switch lockout', a critical alert: the low pressure switch… | Refrigerant undercharge or leak causing repeated low-pressure trips | › |
| Alert 412 | Alert Code 412 in the XP17 table is 'High pressure fault', a moderate alert: discharge pressure rose high… | Outdoor coil dirty or blocked, or outdoor fan not moving air | › |
| Alert 413 | Alert Code 413 in the XP17 table is 'High pressure switch lockout', a critical alert: repeated high pressure… | Outdoor fan failed or coil fouled so heat cannot be rejected in cooling | › |
| Alert 414 | Alert Code 414 in the XP17 table is 'Discharge line temperature fault'. Lennox's own explanation is precise… | Low refrigerant charge raising discharge superheat | › |
| Alert 415 | Alert Code 415 in the XP17 table is 'Discharge line temperature lockout', a critical alert: the high… | Low refrigerant charge or a leak | › |
| Alert 417 | Alert Code 417 in the XP17 table is 'Discharge sensor fault'. Lennox explains the detection exactly: the heat… | Discharge sensor open, shorted or out of resistance range | › |
| Alert 421 | Alert Code 421 in the XP17 table is 'W external miswire fault', a critical alert. Lennox's condition text is… | Low-voltage wiring error on the W circuit after installation or service | › |
Common questions
What does Alert 402 mean on a Lennox XP17?
A system pressure trip: Lennox's table says the compressor protector is open or supply power to the compressor is missing, with high pressure among the listed causes.
What does a slow red flash with the green LED off mean on a Lennox ML14XP1?
A low pressure switch fault. On the CMC1 defrost control, DS2 (green) off with DS1 (red) slow-flashing is Table 3's low pressure switch fault pattern.
Once you know the part you need, browse Lennox Heat pump replacement parts → The parts shelves are organized by brand, with the parts that actually fix these codes.