Lennox Heat pump XP17 Alert 410

What this problem usually means

In the XP17 fault and lockout table (Table 14 in 506586-01), Alert Code 410 is 'Low pressure fault', a moderate alert. The shared solution column for the pressure faults in this table directs: remove blockages or restrictions from coils and fans, check indoor and outdoor fan motors for proper current draws, check system charge using approach and subcooling temperatures, check operating pressures against the unit charging charts, and make sure pressure switches and sensors have secure connections. The listed causes are restricted airflow over the indoor or outdoor coil, improper refrigerant charge, an improper or incorrectly operating metering device, and an incorrect sensor location or connection. A fault, not yet a lockout, means pressure dipped once, not repeatedly.

Likely causes

  1. Restricted airflow over indoor or outdoor coil
  2. Improper refrigerant charge (undercharge or leak)
  3. Metering device incorrect or operating incorrectly
  4. Pressure sensor incorrectly located or poorly connected

How to fix it — step by step

  1. Record Alert 410 and the operating mode before it clears; a single low-pressure fault that returns is on its way to a lockout.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Check the indoor air filter and both coils for blockage first, then remove the control-box panel to inspect the pressure switch and sensor connections the manual tells you to verify.
  4. Have a technician connect gauges, compare operating pressures with the unit charging chart and check charge by approach and subcooling as the manual directs; low pressure with clean airflow points to charge or metering, while normal pressure points to the sensor or its connection.
  5. Replace the filter or clear the restriction yourself; charge, metering and sealed-system work is EPA-certified-technician work only. Confirm a full run with no returning fault.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $5–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.