Lennox Heat pump XP17 Alert 402

What this problem usually means

Table 15 of the XP17 instructions pairs Alert Code 402 with 'System pressure trip'. Lennox's text says it indicates the compressor protector is open or supply power to the compressor is missing. Its listed causes are high head pressure (with checks for the high pressure switch, an overcharged system and non-condensables), poor condenser coil air circulation from a dirty, blocked or damaged coil, and a condenser fan that is not running, including its capacitor, wiring and motor. It clears after four consecutive normal compressor run cycles or after a power reset, so a returning 402 means the pressure problem is still present.

Likely causes

  1. High head pressure from refrigerant overcharge
  2. Dirty, blocked or damaged outdoor coil restricting airflow
  3. Outdoor fan not running: failed capacitor, wiring or motor
  4. High pressure switch open
  5. Return air duct leakage raising system load

How to fix it — step by step

  1. Record Alert 402 and the mode it occurred in before resetting; repeated resets will not fix a pressure trip.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Inspect the outdoor coil and fan from outside, then remove the control-box panel to reach the heat pump control (A175), contactor and fan capacitor (C12).
  4. Clean the coil, confirm the fan runs on a call, and test the run capacitor against its marked rating; a technician should connect gauges and compare pressures with the unit charging chart, because overcharge and non-condensables can only be proven with gauges, not by the alert alone.
  5. Replace a proven-bad capacitor or fan motor, or have charge corrected; Any refrigerant-side repair, charge adjustment or sealed-system work is EPA-certified-technician work only; do not open the refrigerant circuit yourself. Confirm four normal run cycles clear the alert, as the manual states.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $5–$35

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.