Lennox Heat pump ML14XP1 Green LED (DS2) off, red LED (DS1) slow flash

What this problem usually means

On the ML14XP1 defrost control (CMC1), Table 3 of the Lennox installation instructions lists this DS2/DS1 pattern under Fault and Lockout Codes as a low pressure switch fault. The low pressure switch (S87), on the suction line, has opened during a thermostat demand but the control has not yet locked the compressor out. The manual gives the switch settings: it opens when suction pressure drops below 25 psig plus or minus 5, and automatically resets at 40 psig plus or minus 5. Repeated openings in one demand are counted toward the five-strike lockout, so a single fault flash is an early warning, not a nuisance.

Likely causes

  1. Low refrigerant charge or a refrigerant leak
  2. Restricted airflow over the indoor or outdoor coil, including a dirty air filter
  3. Metering device stuck, restricted or operating incorrectly
  4. Low pressure switch failing or a loose switch connection

How to fix it — step by step

  1. Record the exact LED pattern and whether the unit was heating or cooling before cycling power, because a power cycle clears the display and the strike count.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Remove the outdoor unit's control-box access panel to reach the defrost control (CMC1); the diagnostic LEDs, pressure-switch connections and defrost thermostat (S6) connections are all on that board.
  4. With power restored only for testing by a technician, check suction pressure against the manual's switch points (opens below about 25 psig, resets at about 40 psig) and check charge by the unit's charging sticker; low pressure with correct airflow points to charge or metering, while normal pressure with an open switch condemns the switch or its wiring.
  5. If pressure is genuinely low, stop: Any refrigerant-side repair, charge adjustment or sealed-system work is EPA-certified-technician work only; do not open the refrigerant circuit yourself. Replace a proven-bad pressure switch or correct the airflow restriction, then run one full demand and confirm the fault does not return.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $5–$30

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.