Lennox Heat pump XP17 Alert 413
What this problem usually means
Alert Code 413 in the XP17 table is 'High pressure switch lockout', a critical alert: repeated high pressure trips have locked the compressor out. Lennox's pressure-fault cause list for this table is restricted airflow over the indoor or outdoor coil, improper refrigerant charge, an improper or incorrectly operating metering device, and incorrect or improper sensor location or connection to the system, and its solutions are to clear coil and fan blockages, check indoor and outdoor fan motor current draws, check charge using approach and subcooling, compare operating pressures to the unit charging charts, and secure all pressure switch and sensor connections. Lockout is the control's last step before compressor damage from sustained head pressure.
Likely causes
- Outdoor fan failed or coil fouled so heat cannot be rejected in cooling
- Indoor airflow failure in heating (filter, blower or closed registers)
- Refrigerant overcharge
- Failed high pressure switch or its connection
How to fix it — step by step
- Record Alert 413 and stop resetting the unit; sustained high head pressure damages compressors, and the lockout exists to prevent exactly that.
- Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
- Clean the outdoor coil, verify the outdoor fan and indoor blower actually run, replace a clogged filter, and inspect the high pressure switch (S4) and sensor connections shown in the manual's parts arrangement.
- A technician should measure pressures against the charging chart, check charge by approach and subcooling, and test fan current draws; normal measured pressure with a tripped switch condemns the switch, while genuinely high pressure with good airflow condemns charge or metering.
- Replace a proven-bad fan motor, capacitor or pressure switch, or have charge corrected by an EPA-certified technician, then reset once and verify a full clean run.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Outdoor fan motor.
Shop the Outdoor fan motor at Amazon
Also tied to this fault: Air filter - Shop at Amazon
Parts that commonly fix it
- Outdoor fan motorShop at Amazon
- Air filter$5–$30Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number