Lennox Heat pump XP17 Alert 408

What this problem usually means

Alert Code 408 in XP17 Table 15 is 'Welded contactor', a critical alert: the compressor always runs. Lennox gives two causes: the compressor contactor has failed to open, or the thermostat demand signal is not connected to the module. Welded contacts happen when pitted contacts fuse under load, so the compressor keeps running after the call ends, which can overcool, ice the coil and run up wear with no off cycle. The alert clears after one normal compressor run cycle or after a power reset. Because the unit can be live and running when it should be off, treat the outdoor unit as energized until the disconnect is pulled.

Likely causes

  1. Contactor contacts welded or fused shut
  2. Contactor mechanically stuck closed
  3. Thermostat demand signal fault keeping the module output on

How to fix it — step by step

  1. Record Alert 408 and confirm the symptom: compressor running with no thermostat call. Do not assume the unit is off just because the thermostat is satisfied.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed. This fault can leave the compressor energized unexpectedly, so verify dead before touching anything.
  3. Remove the control-box panel and inspect the compressor contactor (K1); welded contacts often show heavy pitting, discoloration or a contactor that does not drop out when its coil loses 24V.
  4. With the call removed, check for 24V at the contactor coil: no coil voltage but line voltage still passing to the compressor proves welded contacts, while coil voltage still present points back to the demand signal or control, as the manual's second cause states. → Shop the contactor at Amazon
  5. Replace a welded contactor (do not file or free stuck contacts), restore the demand wiring if that was the cause, and confirm the compressor now stops when the call ends.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $10–$35

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.