Lennox Heat pump ML14XP1 Green LED (DS2) slow flash, red LED (DS1) off
What this problem usually means
On the ML14XP1 defrost control (CMC1), Table 3 lists green slow flash with red off under Fault and Lockout Codes as a high pressure switch fault. The high pressure switch (S4), on the liquid line, has opened once or more during a demand but the unit is not yet locked out. Lennox gives the switch settings in the same section: it opens when liquid-line pressure rises above 590 plus or minus 15 psig and automatically resets at 418 plus or minus 15 psig. High head pressure usually means heat cannot leave the system, so this fault is the step before a lockout if the cause is not corrected.
Likely causes
- Outdoor fan not running or running weakly in cooling
- Dirty or blocked outdoor coil
- Refrigerant overcharge
- Indoor airflow restriction in heating mode, including a dirty filter
How to fix it — step by step
- Record the LED pattern and the operating mode before cycling power; note whether the outdoor fan was running when the fault appeared.
- Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
- Remove the control-box access panel to reach the defrost control (CMC1) and the S4 high pressure switch connections on the liquid line; also inspect the outdoor coil face and fan from outside the unit.
- Clean a dirty coil and replace a clogged indoor filter, then have a technician measure liquid-line pressure against the manual's switch points (opens above about 590 psig, resets near 418 psig) and check outdoor fan current draw; pressure climbing with a clean coil and running fan points to overcharge or a restriction, while normal pressure with an open switch condemns the switch.
- Correct the airflow or fan cause, or have the charge corrected by an EPA-certified technician; Any refrigerant-side repair, charge adjustment or sealed-system work is EPA-certified-technician work only; do not open the refrigerant circuit yourself. Run one full demand and confirm the fault stays clear.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Outdoor fan motor.
Shop the Outdoor fan motor at Amazon
Also tied to this fault: Air filter - Shop at Amazon
Parts that commonly fix it
- Outdoor fan motorShop at Amazon
- Air filter$5–$30Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.