Burnham Alpine (ALP) series, Sage2.2 control Common Problems
Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 21 problems covered.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
| Problem | What it means | Check first | |
|---|---|---|---|
| Hard Lockout 12 | A hard lockout needing a manual reset: a flame signal was present when there should be no flame, described as… | Defective gas valve letting gas through when closed | › |
| Hard Lockout 18 | A hard lockout needing a manual reset: light-off rate proving failed. The blower is not running at light-off… | Loose connection in the 120 Vac blower wiring | › |
| Hard Lockout 19 | A hard lockout needing a manual reset: purge rate proving failed. The blower is not running at purge rate… | Loose connection in the 120 Vac blower wiring | › |
| Hard Lockout 20 | A hard lockout needing a manual reset: invalid safety parameters. The Sage2.2 control has detected an… | Invalid safety related parameter change in the Sage2.2 control | › |
| Hard Lockout 23 | A hard lockout needing a manual reset: the Sage2.2 control's 24 Vac control power is too high or too low. The… | Loose connection in the 24 Vac power wiring | › |
| Hard Lockout 24 | A hard lockout needing a manual reset: fuel valve error. Power was detected at the fuel valve output when the… | Loose or defective gas valve harness | › |
| Hard Lockout 25 | A hard lockout needing a manual reset: hardware fault, an internal control failure in the Sage control. There… | Internal control failure in the Sage control | › |
| Hard Lockout 4 | A hard lockout needing a manual reset: the supply sensor detected temperatures in excess of 210 degrees F.… | Heating load at the time of the error far below the minimum firing rate of the boiler | › |
| Hard Lockout 5 | A hard lockout needing a manual reset: the DHW sensor detected temperatures in excess of the DHW setpoint.… | DHW load at the time of the error far below the minimum firing rate of the boiler | › |
| Hard Lockout 6 | A hard lockout needing a manual reset: the flue gas (stack) sensor detected temperatures in excess of 204… | Heat exchanger needs to be cleaned | › |
| Soft Lockout 10 | A soft lockout: the stack (flue gas) temperature sensor is shorted or open. The control uses this sensor to… | Shorted or mis-wired stack sensor wiring | › |
| Soft Lockout 11 | A soft lockout: ignition failure, meaning the flame failed after five tries to restart. The boiler tried… | No gas pressure to the boiler | › |
| Soft Lockout 13 | A soft lockout: the flame rod is shorted to ground. The control reads the flame rod circuit as grounded, so… | Shorted or mis-wired flame rod wiring | › |
| Soft Lockout 14 | A soft lockout: the temperature rise between supply and return, the Delta T, is too high. Water is picking up… | Inadequate boiler water flow | › |
| Soft Lockout 15 | A soft lockout: the control is reading a return sensor temperature higher than the supply sensor temperature… | Flow through the boiler reversed, from piping or pump orientation | › |
| Soft Lockout 16 | A soft lockout: the supply water temperature has risen too quickly. Heat is building in the boiler faster… | Inadequate boiler water flow | › |
| Soft Lockout 2 | A soft lockout: the boiler safety limit circuit wired to terminals J6-1, 2 or 3 is open, so the boiler shuts… | Plugged condensate trap, especially if the boiler is not level | › |
| Soft Lockout 3 | A soft lockout: the boiler safety limit or external limit wired to terminal J5-1 is open, shown with ILK Off.… | External limit jumper or device connected to terminals 11 and 12 open | › |
| Soft Lockout 7 | A soft lockout: the return temperature sensor is shorted or open, so the control cannot read return water… | Shorted or mis-wired return sensor wiring | › |
| Soft Lockout 8 | A soft lockout: the supply temperature sensor is shorted or open, so the control has lost its primary water… | Shorted or mis-wired supply sensor wiring | › |
| Soft Lockout 9 | A soft lockout: the domestic hot water temperature sensor is shorted or open. The control cannot manage DHW… | Shorted or mis-wired DHW sensor wiring | › |
All Burnham boiler models & codes →