Burnham Boiler Alpine (ALP) series, Sage2.2 control Soft Lockout 13

What this problem usually means

A soft lockout: the flame rod is shorted to ground. The control reads the flame rod circuit as grounded, so it cannot trust flame sensing and shuts the boiler down. The short is in the rod wiring or the rod itself.

Likely causes

  1. Shorted or mis-wired flame rod wiring
  2. Defective flame rod

How to fix it — step by step

  1. Record the lockout number before resetting.
  2. Safety: switch the service switch off and close the gas shutoff before handling the flame rod or its wiring.
  3. Locate the flame rod at the burner and follow its wire back to the control, looking for insulation worn through where the wire touches the burner or jacket.
  4. Test: disconnect the rod wire and check for continuity to ground along the harness. A harness that tests clean with the rod still showing a ground fault condemns the rod. A short that disappears when a damaged wire section is lifted clear was the wiring.
  5. End at the fix: repair or replace the shorted flame rod wiring. If the wiring tests clean, replace the flame rod.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $10–$60
  • Flame rod$10–$60Shop at Amazon
  • Tools for this job, if you need them$15–$65

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems

See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →