Burnham Boiler Alpine (ALP) series, Sage2.2 control Soft Lockout 3
What this problem usually means
A soft lockout: the boiler safety limit or external limit wired to terminal J5-1 is open, shown with ILK Off. This circuit carries the external limit jumper or device, the low water cutoff jumper or switch, and the low gas pressure switch where fitted. A missing jumper where no device is installed sets this code just as surely as a real open limit.
Likely causes
- External limit jumper or device connected to terminals 11 and 12 open
- Low water cutoff jumper missing, or the cutoff reporting low water
- Low gas pressure switch contacts open where installed
- Loose wiring to a limit device
- Defective external limit device
How to fix it — step by step
- Record the lockout number and read the cause under the blinking Help button.
- Safety: switch the service switch off before testing the limit circuit. Do not run the boiler with a safety limit jumpered out.
- Locate the J5-1 limit circuit terminals and identify what is actually connected: an external limit, a low water cutoff, a low gas pressure switch, or plain jumpers.
- Test: look at the low water cutoff lights. A yellow light on means the system is low on water. Neither yellow nor green lit means check the cutoff harness. Each device or jumper that tests open in turn isolates where the circuit breaks.
- End at the fix: restore the water level if the cutoff is reporting low water, refit any missing jumper, repair loose wiring, and replace a limit device that stays open without cause.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Low water cutoff.
Shop the Low water cutoff at Amazon
Also tied to this fault: External limit device - Shop at Amazon
Parts that commonly fix it
- Low water cutoffShop at Amazon
- External limit deviceShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Soft Lockout 7
- Soft Lockout 8
- Soft Lockout 9
- Hard Lockout 12
- Hard Lockout 18
- Hard Lockout 19
- Hard Lockout 20
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
- Hard Lockout 5
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →