Burnham Boiler Alpine (ALP) series, Sage2.2 control Soft Lockout 14

What this problem usually means

A soft lockout: the temperature rise between supply and return, the Delta T, is too high. Water is picking up too much heat crossing the boiler, which means it is moving too slowly. The boiler restarts once flow improves and the rise comes back into range.

Likely causes

  1. Inadequate boiler water flow
  2. Pump not operating
  3. Pump or piping undersized for the boiler

How to fix it — step by step

  1. Record the lockout number and the supply and return temperatures shown on the display.
  2. Safety: switch the service switch off before working on circulators or piping valves.
  3. Locate the boiler circulator and confirm it runs on a call for heat, and check that the valves in the boiler loop are fully open.
  4. Test: a circulator that runs with a still-wide temperature rise means the pump or piping is undersized for the boiler or partly blocked. A circulator that does not run at all is the fault itself, after its power supply is confirmed. → Shop the boiler circulator at Amazon
  5. End at the fix: restore flow by repairing or replacing the circulator, opening or correcting the piping, and confirm the pump and piping are sized per the manual for the boiler fitted.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems

See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →