Burnham Boiler Alpine (ALP) series, Sage2.2 control Soft Lockout 15

What this problem usually means

A soft lockout: the control is reading a return sensor temperature higher than the supply sensor temperature, and the condition has to be present for at least 75 seconds before the code appears. Return water hotter than supply water means flow through the boiler is reversed, there is no flow at all, or the sensors are crossed.

Likely causes

  1. Flow through the boiler reversed, from piping or pump orientation
  2. No boiler water flow, including air in the system or closed valves
  3. Supply and return sensor wiring reversed
  4. Defective supply or return sensor

How to fix it — step by step

  1. Record the lockout number and both sensor temperatures from the display.
  2. Safety: switch the service switch off before moving sensors or changing piping connections.
  3. Locate the boiler circulator and check its pumping direction against the piping, then locate the supply and return sensors and confirm each sits in the right connection.
  4. Test: purge air from the system and confirm the appropriate valves are open, then run the boiler. Readings that correct themselves once flow direction is right confirm the piping or pump orientation. Readings still crossed on correct flow point at reversed sensor wiring or a bad sensor.
  5. End at the fix: correct the piping or pump orientation, purge the system of air, swap back any reversed sensor wiring, and replace a sensor that still reads wrong against a thermometer.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $25–$80
  • Supply temperature sensor$25–$80Shop at Amazon
  • Return temperature sensor$25–$80Shop at Amazon
  • Tools for this job, if you need them$10–$65

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems

See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →