Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 18
What this problem usually means
A hard lockout needing a manual reset: light-off rate proving failed. The blower is not running at light-off rate when it should, or its speed signal is not being detected by the Sage2.2 control. Without proven airflow at light-off speed the boiler cannot light safely.
Likely causes
- Loose connection in the 120 Vac blower wiring
- Loose or miswired blower speed harness
- Defective blower
How to fix it — step by step
- Record the lockout number and note whether the blower runs at all on a call for heat.
- Safety: switch the service switch off and verify power is off before handling blower wiring. The blower is 120 Vac powered.
- Locate the blower and both its 120 Vac power wiring and its low voltage speed signal harness, following each back to the control.
- Test: reseat both harnesses and retry. A blower that now reaches light-off speed and proves it was a connection fault. A blower that runs but never proves speed on sound harnesses has a failed speed signal or motor.
- End at the fix: repair the loose or miswired blower connections if found. If wiring is sound, replace the blower. Reset manually after the repair. → Shop the blower at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Blower.
Parts that commonly fix it
- BlowerShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Hard Lockout 19
- Hard Lockout 20
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
- Hard Lockout 5
- Hard Lockout 6
- Soft Lockout 10
- Soft Lockout 11
- Soft Lockout 13
- Soft Lockout 14
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →