Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 19
What this problem usually means
A hard lockout needing a manual reset: purge rate proving failed. The blower is not running at purge rate when it should, or its speed signal is not being detected by the Sage2.2 control. Purge airflow has to be proven before every ignition, so this fault stops the start sequence at its first step.
Likely causes
- Loose connection in the 120 Vac blower wiring
- Loose or miswired blower speed harness
- Defective blower
How to fix it — step by step
- Record the lockout number and note whether the blower starts during the purge step.
- Safety: switch the service switch off and verify power is off before handling the 120 Vac blower wiring.
- Locate the blower and inspect its power connections and speed harness for looseness, damage or crossed wires.
- Test: reseat the connections and start a call for heat. Purge speed proven after reseating means the connection was the fault. A blower that will not reach or report purge speed on verified wiring has failed. → Shop the blower at Amazon
- End at the fix: correct the blower wiring if it is loose or miswired. If the wiring is verified good, replace the blower. Reset manually after the repair.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Blower.
Parts that commonly fix it
- BlowerShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Hard Lockout 20
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
- Hard Lockout 5
- Hard Lockout 6
- Soft Lockout 10
- Soft Lockout 11
- Soft Lockout 13
- Soft Lockout 14
- Soft Lockout 15
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →