Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 19

What this problem usually means

A hard lockout needing a manual reset: purge rate proving failed. The blower is not running at purge rate when it should, or its speed signal is not being detected by the Sage2.2 control. Purge airflow has to be proven before every ignition, so this fault stops the start sequence at its first step.

Likely causes

  1. Loose connection in the 120 Vac blower wiring
  2. Loose or miswired blower speed harness
  3. Defective blower

How to fix it — step by step

  1. Record the lockout number and note whether the blower starts during the purge step.
  2. Safety: switch the service switch off and verify power is off before handling the 120 Vac blower wiring.
  3. Locate the blower and inspect its power connections and speed harness for looseness, damage or crossed wires.
  4. Test: reseat the connections and start a call for heat. Purge speed proven after reseating means the connection was the fault. A blower that will not reach or report purge speed on verified wiring has failed. → Shop the blower at Amazon
  5. End at the fix: correct the blower wiring if it is loose or miswired. If the wiring is verified good, replace the blower. Reset manually after the repair.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.