Burnham Boiler Alpine (ALP) series, Sage2.2 control Soft Lockout 8
What this problem usually means
A soft lockout: the supply temperature sensor is shorted or open, so the control has lost its primary water temperature reading. The supply sensor is the control's main protection and control input, so the boiler will not run until it reads correctly again.
Likely causes
- Shorted or mis-wired supply sensor wiring
- Defective supply temperature sensor
How to fix it — step by step
- Record the lockout number before cycling power.
- Safety: switch the service switch off before handling sensor wiring.
- Locate the supply temperature sensor on the supply (outlet) connection at the boiler and follow its harness to the control.
- Test: check the harness for shorts or loose connections, then test the sensor. Open or shorted readings at the sensor on good wiring condemn the sensor. A correct reading at the sensor with the fault still shown points at the harness or control connection.
- End at the fix: repair any shorted or mis-wired sensor wiring. If the wiring tests good, replace the supply temperature sensor.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Supply temperature sensor.
Parts that commonly fix it
- Supply temperature sensor$25–$80Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Soft Lockout 9
- Hard Lockout 12
- Hard Lockout 18
- Hard Lockout 19
- Hard Lockout 20
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
- Hard Lockout 5
- Hard Lockout 6
- Soft Lockout 10
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →