Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 4
What this problem usually means
A hard lockout needing a manual reset: the supply sensor detected temperatures in excess of 210 degrees F. The boiler overheated because heat was not being carried away, and it will not restart until the cause is corrected and the boiler is reset from the Active Fault display or the Sage2.2 control. Repeated resets without fixing the flow problem will keep tripping it.
Likely causes
- Heating load at the time of the error far below the minimum firing rate of the boiler
- Defective system circulator or no flow in the primary loop
- Defective boiler circulator, or no or insufficient flow in the boiler loop
- Control system miswired so boiler operation is permitted when no zones are calling
How to fix it — step by step
- Record the lockout number and the supply temperature history if the control offers it, before resetting.
- Safety: let the boiler cool below the trip temperature before working on it, and switch the service switch off before opening panels.
- Locate the boiler circulator and the system circulator and confirm each runs and moves water on a call for heat.
- Test: fire the boiler with zones calling and watch the supply temperature. Temperature that climbs past 210 degrees F with a circulator running means insufficient flow for the firing rate or a load below minimum fire. Temperature that behaves with zones calling, after tripping with none calling, condemns the control wiring.
- End at the fix: repair or replace the failed circulator, restore flow in the affected loop, and correct control wiring that permits firing with no zones calling. Reset manually only after the cause is fixed.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Boiler circulator.
Shop the Boiler circulator at Amazon
Also tied to this fault: System circulator - Shop at Amazon
Parts that commonly fix it
- Boiler circulatorShop at Amazon
- System circulatorShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Hard Lockout 5
- Hard Lockout 6
- Soft Lockout 10
- Soft Lockout 11
- Soft Lockout 13
- Soft Lockout 14
- Soft Lockout 15
- Soft Lockout 16
- Soft Lockout 2
- Soft Lockout 3
- Soft Lockout 7
- Soft Lockout 8
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →