Burnham Boiler Alpine (ALP) series, Sage2.2 control Soft Lockout 9
What this problem usually means
A soft lockout: the domestic hot water temperature sensor is shorted or open. The control cannot manage DHW temperature without that reading, so it shuts down until the sensor circuit is valid again.
Likely causes
- Shorted or mis-wired DHW sensor wiring
- Defective DHW temperature sensor
How to fix it — step by step
- Record the lockout number before cycling power.
- Safety: switch the service switch off before handling sensor wiring.
- Locate the DHW temperature sensor in the domestic hot water circuit served by the boiler and follow its harness back to the control.
- Test: inspect the wiring for shorts, damage or loose plugs, then test the sensor for an open or short. A failed reading on sound wiring means the sensor itself has failed.
- End at the fix: repair the DHW sensor wiring if it is at fault. If the wiring is sound, replace the DHW temperature sensor.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the DHW temperature sensor.
Parts that commonly fix it
- DHW temperature sensor$25–$80Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Hard Lockout 12
- Hard Lockout 18
- Hard Lockout 19
- Hard Lockout 20
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
- Hard Lockout 5
- Hard Lockout 6
- Soft Lockout 10
- Soft Lockout 11
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →