Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 23

What this problem usually means

A hard lockout needing a manual reset: the Sage2.2 control's 24 Vac control power is too high or too low. The control cannot run its safety circuits reliably on bad control power, and the causes run from loose wiring to a failing transformer.

Likely causes

  1. Loose connection in the 24 Vac power wiring
  2. Loose or miswired 24 Vac harness
  3. Miswired harness causing a power supply short to ground
  4. Defective transformer
  5. Transformer frequency, voltage or VA rating not meeting specifications

How to fix it — step by step

  1. Record the lockout number before resetting.
  2. Safety: switch the service switch off before handling low voltage wiring, and verify power states with a meter rather than by touch.
  3. Locate the control transformer and the 24 Vac harness between the transformer and the Sage2.2 control.
  4. Test: measure the 24 Vac supply at the control with a meter. Voltage in range at the transformer but low or absent at the control condemns the harness or its connections. Voltage already wrong at the transformer output, with correct line voltage in, condemns the transformer.
  5. End at the fix: tighten or repair the 24 Vac connections and correct any short to ground in the harness. Replace the transformer if its output is wrong or its rating does not meet the specification. Reset manually after power is stable.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.