Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 12
What this problem usually means
A hard lockout needing a manual reset: a flame signal was present when there should be no flame, described as flame detected out of sequence. Flame with no call for it means gas is passing when it should not be, and the manual names a defective gas valve as the cause. Treat this as a safety fault, not a nuisance trip.
Likely causes
- Defective gas valve letting gas through when closed
How to fix it — step by step
- Record the lockout number before resetting, and do not reset repeatedly to keep the boiler running.
- Safety: close the gas shutoff at the boiler and leave it closed until the valve is proven. If you smell gas, leave and call the gas supplier.
- Locate the gas valve on the gas train and check the inlet gas pressure against the maximum on the rating plate before condemning the valve, since excessive inlet pressure can hold a valve off its seat.
- Test: inlet pressure below the rating plate maximum with a flame signal still present out of sequence confirms the gas valve is passing gas when it should be shut.
- End at the pinpointed cause: replace the gas valve. This is licensed gas work. Reset manually only after the new valve is installed and tested. → Shop the gas valve at Amazon
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Gas valve.
Parts that commonly fix it
- Gas valve$100–$355Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Hard Lockout 18
- Hard Lockout 19
- Hard Lockout 20
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
- Hard Lockout 5
- Hard Lockout 6
- Soft Lockout 10
- Soft Lockout 11
- Soft Lockout 13
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →