Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 20
What this problem usually means
A hard lockout needing a manual reset: invalid safety parameters. The Sage2.2 control has detected an unacceptable safety related parameter, meaning a parameter change was invalid. Safety parameters define how the boiler protects itself, so the control refuses to run until the parameter set is valid again.
Likely causes
- Invalid safety related parameter change in the Sage2.2 control
How to fix it — step by step
- Record the lockout number and note any recent parameter or control changes.
- Safety: do not experiment with safety parameters to clear this fault. Leave the service switch off except while working in the control menus under the manual procedure.
- Locate the parameter menus on the Sage2.2 control and review the safety related parameter selections against the manual for the boiler model.
- Test: correct any parameter selection that is outside the valid range for the boiler and reset the control. A fault that clears on valid parameters was the invalid change. A fault that persists on a verified parameter set is a control problem.
- End at the fix: restore valid safety parameters and reset the control. If the problem persists, contact the factory route through a technician and expect control replacement.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Sage2.2 control.
Parts that commonly fix it
- Sage2.2 controlShop at Amazon
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
- Hard Lockout 5
- Hard Lockout 6
- Soft Lockout 10
- Soft Lockout 11
- Soft Lockout 13
- Soft Lockout 14
- Soft Lockout 15
- Soft Lockout 16
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →