Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 20

What this problem usually means

A hard lockout needing a manual reset: invalid safety parameters. The Sage2.2 control has detected an unacceptable safety related parameter, meaning a parameter change was invalid. Safety parameters define how the boiler protects itself, so the control refuses to run until the parameter set is valid again.

Likely causes

  1. Invalid safety related parameter change in the Sage2.2 control

How to fix it — step by step

  1. Record the lockout number and note any recent parameter or control changes.
  2. Safety: do not experiment with safety parameters to clear this fault. Leave the service switch off except while working in the control menus under the manual procedure.
  3. Locate the parameter menus on the Sage2.2 control and review the safety related parameter selections against the manual for the boiler model.
  4. Test: correct any parameter selection that is outside the valid range for the boiler and reset the control. A fault that clears on valid parameters was the invalid change. A fault that persists on a verified parameter set is a control problem.
  5. End at the fix: restore valid safety parameters and reset the control. If the problem persists, contact the factory route through a technician and expect control replacement.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.