Burnham Boiler Alpine (ALP) series, Sage2.2 control Soft Lockout 2
What this problem usually means
A soft lockout: the boiler safety limit circuit wired to terminals J6-1, 2 or 3 is open, so the boiler shuts down until the circuit closes again. That circuit bundles the condensate trap float switch, the air pressure switch and the auto reset high limit, and the single most common cause is a plugged condensate trap on a boiler that is not level. The display turns red while the lockout is active and the boiler restarts on its own once the cause clears.
Likely causes
- Plugged condensate trap, especially if the boiler is not level
- Condensate trap float switch contacts open
- Air pressure switch contacts open, including from a blocked vent
- Auto reset high limit contact open, or the auto reset supply sensor reading over 200 degrees F
- Loose wiring to a limit device
- Defective auto reset supply high limit switch
How to fix it — step by step
- Record the lockout number and press the blinking Help button to read the cause the control is reporting.
- Safety: switch the boiler service switch off before opening the trap or panels. Condensate is acidic, so keep it off skin and surfaces.
- Locate the condensate trap at the base of the boiler and check it first: a trap full of debris or a boiler sitting out of level holds the float switch open and sets exactly this code.
- Test: check the air pressure switch circuit and vent for blockage, and check the auto reset high limit. A limit device that tests closed with the trap clean and the vent clear, on wiring that tests continuous, leaves the auto reset supply high limit switch itself as the suspect.
- End at the fix: clean the plugged condensate trap and level the boiler if it is out of level, clear any vent blockage, repair loose limit wiring, and replace a limit switch that tests open at normal temperature.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Condensate trap.
Shop the Condensate trap at Amazon
Also tied to this fault: Auto reset high limit switch - Shop at Amazon; Air pressure switch - Shop at Amazon
Parts that commonly fix it
- Condensate trapShop at Amazon
- Auto reset high limit switchShop at Amazon
- Air pressure switch$50–$205Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.
Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems
- Soft Lockout 3
- Soft Lockout 7
- Soft Lockout 8
- Soft Lockout 9
- Hard Lockout 12
- Hard Lockout 18
- Hard Lockout 19
- Hard Lockout 20
- Hard Lockout 23
- Hard Lockout 24
- Hard Lockout 25
- Hard Lockout 4
See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →