What this problem usually means

A hard lockout needing a manual reset: the DHW sensor detected temperatures in excess of the DHW setpoint. The domestic hot water side overheated, either because the DHW load was too small to absorb the boiler minimum firing rate or because the boiler was allowed to run with no DHW call at all.

Likely causes

  1. DHW load at the time of the error far below the minimum firing rate of the boiler
  2. Control system miswired so boiler operation is permitted when no DHW is calling

How to fix it — step by step

  1. Record the lockout number and the DHW temperature and setpoint shown on the control.
  2. Safety: be careful around the DHW piping and tank connections, which can be hot enough to scald. Switch the service switch off before changing control wiring.
  3. Locate the DHW sensor and the control wiring that enables the boiler on a DHW call.
  4. Test: run a genuine DHW call with normal draw and watch the DHW temperature against setpoint. Temperature that overshoots only on very small draws fits the minimum firing rate cause. Firing with no DHW call at all proves the control wiring fault.
  5. End at the fix: correct the control wiring if the boiler can fire without a DHW call. If wiring is correct, the system design has to give the boiler enough DHW load, which is installer work. Reset manually after correcting the cause.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $25–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.