Burnham Boiler Alpine (ALP) series, Sage2.2 control Hard Lockout 25

What this problem usually means

A hard lockout needing a manual reset: hardware fault, an internal control failure in the Sage control. There is no external sensor or wiring cause listed for this code, because the failure is inside the control itself. A reset is the only field step, and a repeat means replacement.

Likely causes

  1. Internal control failure in the Sage control

How to fix it — step by step

  1. Record the lockout number and how many times it has occurred, from the control fault history if available.
  2. Safety: switch the service switch off before opening the control compartment. No gas or water parts need to be disturbed for this fault.
  3. Locate the Sage control inside the control compartment and inspect its plugs and harness connections for anything loose that could mimic a control failure.
  4. Test: reset the control once and run the boiler through a full call for heat. A single cleared fault that does not return can be monitored. The same hard lockout returning on verified connections is the control failing its own hardware checks.
  5. End at the pinpointed cause: if the problem reoccurs after reset, replace the Sage control. Reset manually after replacement and setup. → Shop the sage2.2 control at Amazon

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the rating plate on the boiler jacket, often behind the front panel. It's the key to the right manual pages and the right parts.

Related Burnham Boiler Alpine (ALP) series, Sage2.2 control problems

See all Burnham Alpine (ALP) series, Sage2.2 control codes & guides →