Burnham Boiler Common Problems
Find your problem in the list below. Each page explains the most likely causes, step-by-step checks you can do yourself, when to call a pro, and the parts that commonly resolve it. 21 problems covered.
Finding your model number: it is on the rating plate on the boiler jacket, often behind the front panel.
Tap any code for its full fix — causes, step-by-step checks, and the parts that commonly fix it.
Alpine with Sage control (soft + hard lockouts)
The Sage control splits faults into Soft Lockouts (conditions the control retries from) and Hard Lockouts (manual reset from the Active Fault display). The same bare number means different things in the two tables, so the entries carry the table name with the number.
| Problem | What it means | Check first | |
|---|---|---|---|
| Hard Lockout 12 | A hard lockout needing a manual reset: a flame signal was present when there should be no flame, described as… | Defective gas valve letting gas through when closed | › |
| Hard Lockout 18 | A hard lockout needing a manual reset: light-off rate proving failed. The blower is not running at light-off… | Loose connection in the 120 Vac blower wiring | › |
| Hard Lockout 19 | A hard lockout needing a manual reset: purge rate proving failed. The blower is not running at purge rate… | Loose connection in the 120 Vac blower wiring | › |
| Hard Lockout 20 | A hard lockout needing a manual reset: invalid safety parameters. The Sage2.2 control has detected an… | Invalid safety related parameter change in the Sage2.2 control | › |
| Hard Lockout 23 | A hard lockout needing a manual reset: the Sage2.2 control's 24 Vac control power is too high or too low. The… | Loose connection in the 24 Vac power wiring | › |
| Hard Lockout 24 | A hard lockout needing a manual reset: fuel valve error. Power was detected at the fuel valve output when the… | Loose or defective gas valve harness | › |
| Hard Lockout 25 | A hard lockout needing a manual reset: hardware fault, an internal control failure in the Sage control. There… | Internal control failure in the Sage control | › |
| Hard Lockout 4 | A hard lockout needing a manual reset: the supply sensor detected temperatures in excess of 210 degrees F.… | Heating load at the time of the error far below the minimum firing rate of the boiler | › |
| Hard Lockout 5 | A hard lockout needing a manual reset: the DHW sensor detected temperatures in excess of the DHW setpoint.… | DHW load at the time of the error far below the minimum firing rate of the boiler | › |
| Hard Lockout 6 | A hard lockout needing a manual reset: the flue gas (stack) sensor detected temperatures in excess of 204… | Heat exchanger needs to be cleaned | › |
| Soft Lockout 10 | A soft lockout: the stack (flue gas) temperature sensor is shorted or open. The control uses this sensor to… | Shorted or mis-wired stack sensor wiring | › |
| Soft Lockout 11 | A soft lockout: ignition failure, meaning the flame failed after five tries to restart. The boiler tried… | No gas pressure to the boiler | › |
| Soft Lockout 13 | A soft lockout: the flame rod is shorted to ground. The control reads the flame rod circuit as grounded, so… | Shorted or mis-wired flame rod wiring | › |
| Soft Lockout 14 | A soft lockout: the temperature rise between supply and return, the Delta T, is too high. Water is picking up… | Inadequate boiler water flow | › |
| Soft Lockout 15 | A soft lockout: the control is reading a return sensor temperature higher than the supply sensor temperature… | Flow through the boiler reversed, from piping or pump orientation | › |
| Soft Lockout 16 | A soft lockout: the supply water temperature has risen too quickly. Heat is building in the boiler faster… | Inadequate boiler water flow | › |
| Soft Lockout 2 | A soft lockout: the boiler safety limit circuit wired to terminals J6-1, 2 or 3 is open, so the boiler shuts… | Plugged condensate trap, especially if the boiler is not level | › |
| Soft Lockout 3 | A soft lockout: the boiler safety limit or external limit wired to terminal J5-1 is open, shown with ILK Off.… | External limit jumper or device connected to terminals 11 and 12 open | › |
| Soft Lockout 7 | A soft lockout: the return temperature sensor is shorted or open, so the control cannot read return water… | Shorted or mis-wired return sensor wiring | › |
| Soft Lockout 8 | A soft lockout: the supply temperature sensor is shorted or open, so the control has lost its primary water… | Shorted or mis-wired supply sensor wiring | › |
| Soft Lockout 9 | A soft lockout: the domestic hot water temperature sensor is shorted or open. The control cannot manage DHW… | Shorted or mis-wired DHW sensor wiring | › |
Common questions
What is the difference between a Burnham soft lockout and a hard lockout?
A soft lockout is a condition the Sage control keeps retrying or clears when the condition clears - a sensor fault or a safety limit opening. A hard lockout stops the boiler until you reset it from the Active Fault display, and it is the table for the serious faults: high limits, flame out of sequence, fuel valve errors.
What does Soft Lockout 11 mean on a Burnham Alpine?
Ignition failure: the flame failed after 5 tries. The manual's checks cover gas pressure, unpurged air in the line, the electrode, burner ground, the ignition cable and the air-fuel mixture.
Once you know the part you need, browse Burnham Boiler replacement parts → The parts shelves are organized by brand, with the parts that actually fix these codes.